11
REFRIGERANT SYSTEM DIAGRAM
7
OUTDOOR UNIT
Unit:mm
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Ambient
Temperature
Thermistor
RT65
Discharge
temperatuer
thermistor
RT62
Flared connection
Stop valve
(with strainer)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe
[
9.52
(with heat insulator)
Refrigerant pipe
[
6.35
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
Capillary tube
[
3.0
✕
[
2.0
✕
200
Expansion
valve
Muffler
Muffler
MUZ-A09YV -
MUZ-A09YVH -
MUZ-A12YV -
MUZ-A12YVH -
E1
E1
E1
E1
Refrigerant Piping
Max. length
A
w
Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
w
Max. Height
difference 12m
Indoor
unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Max. length : m
A
20
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
Liquid
6.35
Outdoor unit
Piping size O.D : mm
Length of connecting pipe : m
Model
MUZ-A09YV -
E1
MUZ-A09YVH -
E1
MUZ-A12YV -
E1
MUZ-A12YVH -
E1
OB328 A--1qxp 04.4.26 4:49 PM Page 11