10
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-GS30NA
MUZ-GS30NAH
MUZ-GS36NA
MUZ-GS36NAH
MUY-GS30NA
MUY-GS36NA
100
50
5/8
1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
70
80
90
100
MUZ-GS30NA
MUZ-GS30NAH
MUZ-GS36NA
MUZ-GS36NAH
MUY-GS30NA
MUY-GS36NA
4 lb. 0 oz.
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)