23
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-GL09NA
MUZ-GL09NAH
MUY-GL09NA
MUZ-GL12NA
MUZ-GL12NAH
MUY-GL12NA
65
40
3/8
1/4
MUZ-GL15NA
MUZ-GL15NAH
MUY-GL15NA
65
40
1/2
1/4
MUZ-GL18NA
MUZ-GL18NAH
MUY-GL18NA
100
50
1/2
1/4
MUZ-GL24NA
MUZ-GL24NAH
MUY-GL24NA
100
50
5/8
3/8
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
65
MUZ-GL09NA
-
U1
MUZ-GL09NA
-
U2
MUZ-GL09NAH
-
U1
MUZ-GL09NAH
-
U2
MUY-GL09NA
-
U2
2 lb. 5 oz.
0
1.08
3.24
5.40
7.56
8.64
MUZ-GL09NA
-
U8
MUZ-GL09NAH
-
U8
MUY-GL09NA
-
U1
MUZ-GL12NA
MUZ-GL12NAH
MUY-GL12NA
MUZ-GL15NA
MUZ-GL15NAH
MUY-GL15NA
2 lb. 9 oz.
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
OBH733G
Содержание MUY-GL09NA-U1
Страница 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733G ...
Страница 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733G ...
Страница 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733G ...
Страница 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733G ...
Страница 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733G ...
Страница 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733G ...
Страница 15: ...15 MUZ GL18NA OBH733G ...
Страница 16: ...16 MUZ GL18NAH OBH733G ...
Страница 17: ...17 MUY GL18NA OBH733G ...
Страница 18: ...18 MUZ GL24NA OBH733G ...
Страница 19: ...19 MUZ GL24NAH OBH733G ...
Страница 20: ...20 MUY GL24NA OBH733G ...
Страница 75: ...75 OBH733G ...