background image

10

8-1. TIMER SHORT MODE

For service, the following set time can be shortened by bridging the timer short mode point on the electronic control P.C. 
board. (Refer to 10-7.)
Set time: 3-minute 

 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is 

shortened by bridging the timer short mode point.)

NOTE

: While the relay 52C is ON, the compressor starting time cannot be shortened.

MSZ-WN25VA  MSZ-WN35VA

8

SERVICE FUNCTIONS

NOTE:

• 

The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote 

controller.

• 

If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-

celled.

• 

If the unit has been turned OFF with the remote controller before power failure, the auto restart function does not work 

as the power button of the remote controller is off.

• 

To prevent the breaker from tripping OFF due to the rush of starting current, systematize other home appliance not to 

turn ON at the same time.

• 

When some air conditioners are connected to the same supply system, if they are operated before power failure, the 

starting current of all the compressors may flow simultaneously at restart.

  Therefore, the special countermeasures are required to prevent the main voltage-drop or the rush of the starting current 

by adding to the system that allows the units to start one by one.

JR77

Indoor electronic 
control P.C. board

CN10A

C

N

111

CN151

CN112

CN110

8-3. AUTO RESTART FUNCTION

When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed 
are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in 
the same mode just before the shutoff of the main power. 

Operation

 

If the main power has been cut, the operation settings remain.

 

After the power is restored, the unit restarts automatically according to the memory. 

  (However, it takes at least 3 minutes

 

for the compressor to start running.)

How to disable “AUTO RESTART FUNCTION”

 

Turn off the main power for the unit.

 

Cut the Jumper wire to JR77 on the indoor electronic control P.C. board. (Refer to 10-7.)

8-2. HOW TO SET REMOTE CONTROLLER EXCLUSIVELY FOR A PARTICULAR INDOOR UNIT 

A maximum of 4 indoor units with wireless remote controllers can be used in a room.
To operate the indoor units individually with each remote controller, assign a number to each remote controller according 
to the number of the indoor unit.

 

This setting can be set only when all the following conditions are met:

 

• The remote controller is powered OFF.

 

(1) Hold down 

 button on the remote controller for 2 seconds to enter the pairing mode.

 (2) 

Press   button again and assign a number to each remote controller. 

 

 

Each press of 

 button advances the number in the following order: 1 

 2 

 3 

 4.

 (3) 

Press   button to complete the pairing setting.

After you turn the breaker ON, the remote controller that first sends a signal to an indoor unit will be regarded as the 
remote controller for the indoor unit.
Once they are set, the indoor unit will only receive the signal from the assigned remote controller afterwards.

OBH764

Содержание MSZ-WN25VA - E1

Страница 1: ...G 15 11 DISASSEMBLY INSTRUCTIONS 27 Outdoor unit service manual MUZ WN VA Series OBH765 MSZ WN25VA MSZ WN35VA INDOOR UNIT Models MSZ WN25VA E1 MSZ WN35VA E1 SERVICE MANUAL NOTE RoHS compliant products have G mark on the spec name plate No OBH764 PARTS CATALOG OBB764 Questo manuale d istruzione è fornito da trovaprezzi it Scopri tutte le offerte per Mitsubishi Condizionatore MSZ WN25 o cerca il tuo...

Страница 2: ...h the refrigerant Do not touch the hot or cold areas in the refrigeration cycle When the repair or the inspection of the circuit needs to be done without turning off the power exercise great caution not to touch the live parts Use the specified refrigerant only Never use any refrigerant other than that specified Doing so may cause a burst an explosion or fire when the unit is being used serviced o...

Страница 3: ...3 1 TECHNICAL CHANGES MSZ WN25VA E1 MSZ WN35VA E1 1 New model OBH764 ...

Страница 4: ... for remote controller 2 Air cleaning filter Silver ionized air purifier filter 1 2 PART NAMES AND FUNCTIONS Operation indicator lamp Remote control receiving section Horizontal vane Air inlet Air lter Air purifying filter Front panel Air outlet Heat exchanger Emergency operation switch Remote controller Air cleaning lter Silver ionized air purifier filter Display section OBH764 ...

Страница 5: ...Med 330 Low 210 Sound level Cooling Super High dB A 43 46 High 37 38 Med 30 31 Low 22 Heating Super High dB A 43 44 High 37 Med 30 Low 23 Fan speed Cooling Super High rpm 1 080 1 240 High 880 930 Med 710 730 Low 550 Heating Super High rpm 1 120 1 150 High 900 Med 710 Low 520 Fan speed regulator 4 Remote controller model SG17A NOTE Test conditions are based on ISO 5151 Cooling Indoor Dry bulb tempe...

Страница 6: ...10 MSZ WN25VA INDOOR UNIT WALL MICROPHONE 0 8m 1m 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR BAND CENTER FREQUENCIES Hz COOLING FUNCTION SPL dB A LINE Super High FAN SPEED HEATING Test conditions Cooling Dry bulb temperature 27 C Wet bulb temperature 19 C Heating Dry bulb temperature 20 C...

Страница 7: ...8 41 42 249 248 21 5 3 167 157 207 5 206 5 172 14 46 60 193 19 PIPING INSULATION Ø35 O D LIQUID LINE Ø7 0 0 39m FLARED CONNECTION Ø6 35 GAS LINE Ø9 52 0 34m FLARED CONNECTION Ø9 52 DRAIN HOSE INSULATION Ø28 CONNECTED PART Ø16 O D AIR IN INSTALLATION PLATE PIPING DRAIN HOSE AIR OUT 11 26 OBLONG HOLE 11 20 OBLONG HOLE INSTALLATION PLATE INDOOR UNIT WALL HOLE Ø65 OBH764 ...

Страница 8: ...8 MSZ WN25VA MSZ WN35VA 6 WIRING DIAGRAM OBH764 ...

Страница 9: ...ure thermistor RT11 Flared connection Refrigerant flow in cooling Refrigerant flow in heating Refrigerant pipe ø9 52 with heat insulator Refrigerant pipe ø6 35 with heat insulator Indoor coil thermistor RT12 Indoor coil thermistor RT13 Unit mm 7 REFRIGERANT SYSTEM DIAGRAM OBH764 ...

Страница 10: ... 8 3 AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller the operation mode the set temperature and the fan speed are memorized by the indoor electronic control P C board AUTO RESTART FUNCTION automatically starts operation in the same mode just before the shutoff of the main power Operation If the main power has been cut the operation settings remain After the powe...

Страница 11: ...of the indoor unit turns on with a beep tone 2 Select COOL mode with OPERATION SELECT button 3 Press TEMPERATURE buttons TOO WARM or TOO COOL button to select the desired temperature The setting range is 16 31 C 1 Coil frost prevention The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil from frosting When the temperature of indoor ...

Страница 12: ...rol This mode continues until the temperature of indoor heat exchanger falls 3 Defrosting Defrosting starts when the temperature of outdoor heat exchanger becomes too low The compressor stops once the indoor outdoor fans stop the 4 way valve reverses and the compressor re starts This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes 3 Positioning To conf...

Страница 13: ...t energy can be saved To cancel this operation select a different mode or press one of the following buttons in ECONO COOL operation ECONO COOL or VANE CONTROL button 9 5 TIMER OPERATION ON OFF TIMER 1 How to set the time 1 Check that the current time is set correctly NOTE Timer operation will not work without setting the current time Initially 0 00 blinks at the current time display of TIME MONIT...

Страница 14: ...rom the remote controller In the latter case normal operation will start NOTE Do not press EMERGENCY OPERATION switch during normal operation Operation mode COOL HEAT Set temperature 24 C 24 C Fan speed Med Med Horizontal vane Auto Auto The operation mode is indicated by the Operation Indicator lamp as follows Operation Indicator lamp EMERGENCY COOL EMERGENCY HEAT STOP Lighted Not lighted 9 7 3 MI...

Страница 15: ... drop caused by the battery replacement 3 Do not use the leaking batteries Press RESET button with a thin instrument and then use the remote controller Remove the back lid and insert batteries Then reattach the back lid 10 1 CAUTIONS ON TROUBLESHOOTING 1 Before troubleshooting check the following 1 Check the power supply voltage 2 Check the indoor outdoor connecting wire for miswiring 2 Take care ...

Страница 16: ...ck the blinking pattern and identify the abnormal point by referring to the indoor unit failure recall mode table Refer to 10 2 2 Make sure to check at least 2 consecutive blinking cycles 2 Releasing the failure mode recall function Release the failure mode recall function by the following procedures Turn OFF the power supply and turn it ON again Press RESET button of the remote controller The out...

Страница 17: ...of the main indoor coil ther mistor the sub indoor coil thermistor 10 7 3 time flash 2 5 second OFF Serial signal The serial signal from outdoor unit is not re ceived for a maximum of 6 minutes Refer to 10 6 How to check miswiring and serial signal error 11 time flash 2 5 second OFF Indoor fan motor The rotational frequency feedback signal is not emitted for the 12 seconds after the indoor fan mot...

Страница 18: ...peration means the operation within 30 minutes after EMERGENCY OPERA TION switch is pressed Refer to outdoor unit service manual Upper lamp Flash on and off at 0 5 sec ond intervals Cause Indoor Outdoor unit Miswiring or trouble of se rial signal Upper lamp 2 time flash Cause Indoor unit Trouble of room temperature indoor coil thermistor Upper lamp 3 time flash Cause Indoor unit Trouble of indoor ...

Страница 19: ...ctronic control P C board 5 Outdoor power sys tem Upper lamp flashes 5 time flash 2 5 second OFF It consecutively occurs 3 times that the com pressor stops for overcurrent protection or start up failure protection within 1 minute after start up Refer to How to check of in verter compressor Refer to outdoor unit service manual Check the stop valve 6 Outdoor thermistors Upper lamp flashes 6 time fla...

Страница 20: ...th a tester Refer to 10 7 Test point diagram and voltage 2 Indoor electronic control P C board for the chart of thermistor Indoor coil thermistor RT12 RT13 Indoor fan motor MF Check 10 6 Vane motor MV Measure the resistance between the terminals with a tester Part temperature 10 30 C Color of the lead wire Normal RED BLK 235 255 Ω BLK BLK RED BLK BLK ROTOR OBH764 ...

Страница 21: ...is pressed the voltage measured at 2 above goes 0 VDC although the indoor P C board is normal Does the voltage between CN211 and on the power P C board rise to the range of 3 to 6 VDC within 12 seconds after EMERGENCY OPERATION switch is pressed Replace the indoor fan motor Yes No The indoor fan motor error has occurred and the indoor fan repeats 12 second ON and 30 second OFF 3 times and then sto...

Страница 22: ...tart type within the range of 1 m 2 Yes No Reinstall the unit away from lights Attach a filter on receiving part Replace the indoor electronic control P C board Including the receiver 1 Look at the image of the signal transmitting section of the remote controller through the monitor of a digital camera or a camera phone It is normal if the LED of the signal transmitting section lights up when the ...

Страница 23: ...d and the indoor fan motor Replace the indoor electronic control P C board Measure the resistance of the vane motor coil Refer to 10 5 Short circuit Replace the vane motor and the indoor electronic control P C board 1 The fan motor connector s lead wire is red whereas is black 2 Connect of the tester to fan motor connector s lead wire and to lead wire otherwise the resistance cannot be measured pr...

Страница 24: ...inverter P C board in the outdoor unit repeat 3 6 second OFF and 0 8 second ON quick blinking for 3 minutes after the outdoor unit is energized Check the blinking pattern within 3 minutes after LED is turned on Af ter 3 minutes LED will blink 6 times whether the inverter P C board in the outdoor unit is normal or not No Replace the inverter P C board in the outdoor unit 2 Yes A 2 Be careful of 140...

Страница 25: ...he installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios FM AM broadcast shortwave 2 Channel frequency broadcast station affected by the electromagnetic noise 3 Channel frequency broadcast station unaffected by the electromagnetic noise 4 Layout of indoor outd...

Страница 26: ...1 3 6 VDC 15 VDC GND High voltage DC 325 VDC 0 or 15 VDC Indoor terminal block connecting TAB2 Timer short mode point Refer to 8 1 Room temperature thermistor RT11 CN111 Connector to Indoor coil thermistor RT12 RT13 CN112 Vane motor CN151 Connector to indoor power P C board CN10A 12V DC 5V DC To disable Auto restart function cut the Jumper wire to JR77 Refer to 8 3 Emergency operation switch E O S...

Страница 27: ...erminal with this connector has the locking mechanism Slide the sleeve Pull the terminal while pushing the locking lever Hold the sleeve and pull out the terminal slowly Connector Sleeve Locking lever Terminal with locking mechanism Detaching points The terminal which has the locking mechanism can be detached as shown below There are 2 types refer to 1 and 2 of the terminal with locking mechanism ...

Страница 28: ...rical cover and remove the electrical cover 8 Disconnect the following connectors Indoor power P C board CN211 Indoor fan motor CN201 TAB1 TAB2 Terminal block CN20A To the indoor electronic control P C board 9 Remove the upper catch of the electrical box and pull out the electrical box To attach the electrical box pass the wires connecting the indoor power P C board and the indoor electronic contr...

Страница 29: ...e back side of the control P C board holder 5 Unhook the catches of the control P C board holder and open the control P C board holder 6 Remove the indoor electronic control P C board from the control P C board holder 4 Removing the vane motor 1 Remove the panel Refer to 1 Remove the corner box 2 Remove the control P C board holder and the electrical box Refer to 2 3 Pull out the drain hose from t...

Страница 30: ...lead wire of the fan motor from the motor band 10 Disengage the hooks of the motor band and remove the motor band Pull out the indoor fan motor 11 Remove the indoor coil thermistor from the heat exchanger Install the indoor coil thermistor in its former position when assembling it 12 Remove the screws fixing the left side of the heat exchanger 13 Lift the heat exchanger and pull out the line flow ...

Страница 31: ...ked position Do not pull the lead wire when removing the indoor coil thermistor Holder shape Clip shape When fixing the indoor coil thermistor to the clip shape holder shape part the lead wire should point down 1 Set the indoor coil thermistor in the center of the clip shape part 2 Check the marked mounting position 3 Mount the clip shape part Position and procedure for mounting the clip shape par...

Страница 32: ...ht 2016 MITSUBISHI ELECTRIC CORPORATION Published Dec 2016 No OBH764 Made in Japan Specifications are subject to change without notice HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: