C Check of indoor P.C. board and indoor fan motor
Turn OFF the power supply.
Remove indoor fan motor connector CN211
from indoor power P.C. board and vane
motor connector CN151 from the indoor
electronic control P.C. board and turn ON
the power supply.
Does the unit operate with the remote
controller?
Does OPERATION INDICATOR lamp light
up by pressing EMERGENCY OPERATION
switch?
Yes
No
Measure the resistance of indoor fan
motor. Refer to 10-5.
Short circuit :
Replace the indoor fan motor.
Turn OFF the power supply.
Check both “parts side” and “pattern
side” of the indoor terminal P.C.
board visually.
Replace the varistor (NR11)
and fuse (F11). 3
Are the varistor (NR11)
burnt and the fuse (F11)
blown?
No
No
Yes
Yes
Be sure to check both the fuse
and the varistor in any case.
Is the fuse (F11) blown
only?
Measure the resistance between
CN211 (+) and (-) of indoor fan
motor
connector. 1, 2
Yes
Is the resistance 1M
Ω
or more?
No
Replace the fuse (F11).
3
Measure the resistance of the resis-
tor (R111) on the indoor power P.C.
board.
No
Is the resistance approx.
4
Ω
?
No
Replace the indoor power P.C. board,
terminal P.C. board and the indoor fan
motor.
Replace the indoor power P.C. board and the
indoor terminal P.C. board.
Measure the resistance of the vane
motor coil. Refer to 10-5.
Short circuit :
Replace the vane motor and the indoor
electronic control P.C. board.
1. The fan motor connector's lead
wire is red, whereas is black.
2. Connect "+" of the tester to fan
motor connector's lead wire, and
“–” to lead wire, otherwise the
resistance cannot be measured
properly.
3. Please replace the fuse after
removing the indoor terminal P.C.
board from the electrical box.
Is the approx. 5 VDC between 5 V
(+) and JPG (GND) (-) of the indoor
electronic control P.C. board? Is there
approx. 9 to 13 VDC between 12 V
(+) and JPG (GND) (-) of the indoor
electronic control P.C. board.
Are connector CN10A on the
indoor electronic control P.C.
board or lead wires discon-
nected?
Yes
Replace the indoor fan motor.
Yes
Connect the connector or repair discon-
nection.
Yes
No
Measure the resistance of indoor fan
motor. Refer to 10-5.
Is the resistance
normal?
Replace the fuse (F11)
and the indoor fan motor.
3
Yes
No
HC35
HC25
JPG (GND)
12 VDC
5 VDC
CN10A
CN211
(
HC35
)
Indoor power P.C.board
Indoor electronic
control P.C.board
Fuse (F11)
Indoor terminal
P.C.board
Varistor
(NR11)
R111
CN211
(
HC25
)