26
The left lamp of OPERA-
TION INDICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication (Out-
door P.C. board)
Condition Remedy
Indoor/outdoor
unit failure mode
recall function
LED 1
LED 2
11-time
fl
ash
Converter
5 times Goes out A failure is detected in the operation of the converter dur-
ing operation.
• Check the voltage of
power supply.
• Replace the power board.
—
Bus-bar voltage (1)
5 times Goes out The bus-bar voltage exceeds 400 V or falls to 200 V or
below during compressor operating.
Bus-bar voltage (2)
Even if this protection stop
is performed continuously 3
times, it does not mean the
abnormality in outdoor power
system.
6 times Goes out The bus-bar voltage exceeds 400 V or falls to 50 V or
below during compressor operating.
• Check the voltage of
power supply.
• Replace the outdoor
electronic control P.C.
board.
OBH502E