134
OPERATING PROCEDURE
PHOTOS
3. Removing the propeller fan and the outdoor fan
motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller fan nut.
(3) Remove the propeller fan.
NOTE : Loose the propeller fan in the rotating direction for
removal.
When attaching the propeller fan, align the mark on the
propeller fan and the motor shaft cut section.
Set the propeller fan in position by using the cut on the
shaft and the mark on the propeller fan.
(4) Remove lead clamps and disconnect the outdoor fan motor
connector.
(5) Remove screws fixing the fan motor.
(6) Remove the outdoor fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
(10) Remove the compressor.
NOTE
●
Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
2
(0 MPa) .
●
Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
Photo 6
Photo 5
Propeller fan
Propeller fan nut
Screws of the
outdoor fan motor
Lead clamps
Hook
Compressor
Terminal cover
Suction pipe
Discharge pipe
Compressor
set nuts
Glass
terminal
Outdoor
fan motor
connector
OB307A5.qxp 03.2.19 4:14 PM Page 134