4.OPERATING RANGE
(1)POWER SUPPLY
(2)OPERATION
5.ADDITIONAL REFRIGERANT CHARGE (R-22(oz))
Indoor unit
115V 60Hz 1
[
208/230V 60Hz 1
[
(3wires)
Min. 198V 208V 230V Max. 253V
Min. 103v—Max. 127V
Outdoor unit
MS09NW
MUM18NW
Models
Rating
Guaranteed Voltage
Function
Cooling
Indoor
Outdoor
78%
–
DB (˚F)
80
95
67
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
WB (˚F)
67
71
57
DB (˚F)
95
115
67
WB (˚F)
–
–
–
Intake air
temperature
Condition
Model
Outdoor unit
precharged
(up to 25ft)
Refrigerant piping length (one way)
MS09NW
✕
2
MUM18NW
1 Ibs 14 oz
✕
2
25ft
30ft
33ft
40ft
45ft
49ft
0
1
1
2
2
3
6.MAX. REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE
MSM18NW
Indoor unit A
MS09NW
Max. Length
49ft
❋
Max. Height
difference 25ft
Indoor unit B
MS09NW
Outdoor unit
MUM18NW
Max. Length
49ft
7.PIPING PREPARATION
1
Table below shows the specifications of pipes commercially available.
2
Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3
Refrigerant bending radius must be 10cm or more.
Outside diameter
Insulation
UNIT No.
Pipe
inch
thickness(in)
Insulation material
and
UNIT
For liquid
1/4
1/4
Heat resisting foam plastic
For gas
3/8
1/4
0.045 specific gravity
B
A
OB202-1.qxp 26/9/97 11:07 AM Page 8