4-1. PURGING PROCEDURES AND LEAK TEST

1)  Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The stop 

valves are fully closed and covered in caps in initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on the 

gas pipe side of the outdoor unit.

4-2. TEST RUN

1)  Insert power supply plug into the power outlet and/or turn on the 

breaker.

2) Press the E.O. SW. Test run will be performed for 30 minutes. 

If the upper lamp of the operation indicator blinks every 0.5 
seconds, inspect the indoor/outdoor unit connecting wire (A) for 
mis-wiring.  After the test run, emergency COOL mode (24°C 
COOL) will start.

3)  To stop operation, press the E.O. SW several times until all LED 

lamps turn off. Refer to operating instructions for details. 

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller and check that an electronic sound is 
heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
•  Once the compressor stops, the restart preventive device operates so the compressor 

will not operate for 3 minutes to protect the air conditioner.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is stopped 
during operation, such as during blackouts, the function automatically starts operation in 
the previous setting once the power supply is resumed. (Refer to the operating instructions 
for details.) 

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air condi-

tioner (how to use the remote controller, how to remove the air filters, how to remove or 
put the remote controller in the remote controller holder, how to clean, precautions for 
operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the 
procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe 

side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it 

can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation.
  To start the emergency operation in COOL mode, disconnect the power supply plug 

and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn 
on the breaker, and then press the E.O. SW once. (The emergency COOL operation can 
be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.
 

Press the E.O. SW several times until all LED lamps turn off. Refer to operating instruc-
tions for details.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4)  Check the vacuum with gauge manifold valve, then close gauge manifold valve, and stop 

the vacuum pump.

5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve remains 

in the same position. Confirm that pressure gauge shows –0.101 MPa [Gauge] (–760 
mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.
7) After refrigerant pipes are connected and evacuated, fully open all stop valves on both 

sides of gas pipe and liquid pipe. Operating without fully opening lowers the performance 
and this causes trouble.

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. SW or 

the remote controller before turning off the power supply. Not doing so will cause the 
unit to start operation automatically when power supply is resumed.

To the user

•  After installing the unit, make sure to explain the user about auto restart function. 
•  If auto restart function is unnecessary, it can be deactivated. Consult the service 

representative to deactivate the function. Refer to the service manual for details.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

5.  RELOCATION AND MAINTENANCE

8)  Refer to 1-3., and charge the prescribed amount of refrigerant if needed. Be sure to charge 

slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the system may 
be changed and affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
10) Leak test

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation 
plate.
When releasing the corner part, release both left and right 
bottom corner part of indoor unit and pull it downward and 
forward as shown in the figure on the right.

If the above method cannot be used

Remove the panel. Then, insert hexagonal wrenches into the square holes on the left and 
right sides of the unit and push them up as shown in the following figure. The bottom of the 
indoor unit lowers and releases the hooks.

Removal procedure

1) Remove the 2 screws which fix the panel assem-

bly.

2) Remove the panel assembly. Be sure to remove its 

bottom end first.

Installation procedure

1) Install the panel assembly following the removal 

procedure in reverse. 

2) Be sure to press the positions as indicated by the 

arrows in order to attach the assembly completely 
to the unit.

Push

Lower

Square hole

Emergency  
operation 
switch
(E.O. SW)

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

Stop valve for 
GAS

Stop valve cap
(Torque 19.6 to 
29.4 N•m, 200  
to 300 kgf•cm)

Vacuum pump (or the vacuum 
pump with the function to 
prevent the back flow)

Compound pressure gauge 
(for R410A)

0.101 MPa  

(

760 mmHg)

Handle 
Low

Charge hose 
(for R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve When attaching the control valve to 

the service port, valve core may de-
form or loosen if excess pressure is 
applied. This may cause gas leak.

Service port

Body

Close

Open

Control valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

Service port cap
(Torque 13.7 to 
17.7 N•m, 140 to 
180 kgf•cm)

*4 to 5 turns

Stop valve 
for LIQUID

Pressure gauge
(for R410A)

Charge hose 

Gauge manifold valve 
(for R410A)

Handle High

Adapter for 
preventing the 
back flow

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 
100-8310, JAPAN
AUTHORIZED REPRESENTATIVE IN EU:
MITSUBISHI ELECTRIC EUROPE B.V.
HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.

This product is designed and intended for use in the residential, commercial and 
light-industrial environment.

The product at hand is 
based on the following 
EU regulations:

•  Low Voltage Directive 2006/95/EC
•  Machinery Directive 2006/42/EC
•  Electromagnetic Compatibility Directive 2004/108/EC

Note:

Complete pumping down within 3 minutes. After 3 minutes, the unit will automatically 
stop to prevent a burst in case that air is mixed up.

Содержание MS-GF20VA

Страница 1: ...ab normally high This could cause the pipes to burst or injury N When installing the unit securely connect the refrigerant pipes before starting the compressor If the compressor is started before the refrigerant pipes are connected and when the stop valve is open air could be drawn in and the pressure in the refrigeration cycle could become abnormally high This could cause the pipes to burst or in...

Страница 2: ...code requirements Liquid pipe Gas pipe Felt tape 7 Indoor outdoor unit connecting wire A Piping tape G Indoor unit Wall hole sleeve C Cut off the extra length Pipe fixing band E Be sure to use wall hole sleeve C to prevent in door outdoor connecting wire A from contacting metal parts in the wall and to prevent damage by rodents in case the wall is hollow Wall hole cover D Seal the wall hole gap wit...

Страница 3: ... 3 Using piping tape G apply taping starting from the entry of outdoor unit Stop the end of piping tape G with tape with adhesive agent attached When piping have to be arranged through above ceiling closet or where the temperature and humidity are high wind additional commercially sold insulation to prevent condensa tion Rear right or downward piping 1 Put the refrigerant piping and the drain hose...

Страница 4: ...sides of gas pipe and liquid pipe Operating without fully opening lowers the performance and this causes trouble Caution After test run or remote signal reception check turn off the unit with the E O SW or the remote controller before turning off the power supply Not doing so will cause the unit to start operation automatically when power supply is resumed To the user After installing the unit mak...

Страница 5: ...25 35VE3 MUZ EF25 35VE Installation Manual JG79A476H01 MSZ FH25 35 and MUZ FH25 35 Declaration of Conformity MSZ FH25 35VE2 MUZ FH25 35VE Declaration of Conformity CE2016B25 MUZ FH25 35 Service Manual OBH624B MUZ FH25 50VE Parts Catalogue OBB624B ...

Отзывы: