10-5. TROUBLE CRITERION OF MAIN PARTS
Part name
Check method and criterion
Figure
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12)
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "1. Indoor electronic control
P.C. board", for the chart of thermistor.
MS-GF20/25/35VA
Indoor fan motor (MF)
INNER FUSE
145 °C CUT OFF
Measure the resistance with a tester.
(Part temperature 10 ~ 30 °C)
Color of the lead wire
Normal
WHT-BLK
334 Ω ~ 362 Ω
BLK-RED
370 Ω ~ 402 Ω
MS-GF50/60/80VA
Indoor fan motor (MF)
Check 10-6. "Check of indoor fan motor".
MS-GF20/25/35VA
Horizontal vane motor
(MV)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED-BLK
223 Ω ~ 268 Ω
BLK
BLK
RED
BLK
BLK
ROTOR
MS-GF50/60/80VA
Horizontal vane motor
(MV1)
Vertical vane motor
(MV2)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
Horizontal vane motor (MV1)
RED-BLK
313 ~ 375 Ω
Vertical vane motor (MV2)
268 ~ 322 Ω
MAIN
AUX.
BLK
RED WHT
FUSE
OBH621A