background image

1

1

2

H

D

C

7

B

G

3

6

E

F

K

4

A

7 mm or more

500 mm or more

100 mm or more

100 mm or m

ore

500 mm or mor

e

350 mm or mor

e

Note:

Do not 
obstruct the 
air outlet.

72 mm or more 

100 mm or more for left and left 

back piping (using spacer)

120 mm 

or mo

re

200 mm 

or mo

re

5

Be careful the 
drain hose is not 
raised.

Separate the 2 connecting pipes and 
apply insulation individually.

8 mm thickness thermal insulation 
plastic

Decide the installation position using mark on the installation 
plate indicating the indoor unit size as reference.

When the piping is to be attached to 
a wall containing metals (tin plated) or 
metal netting, use a chemically treated 
wooden piece 20 mm or thicker be-
tween the wall and the piping or wrap 
7 to 8 turns of insulation vinyl tape 
around the piping.

Lock the catch.

Front

Piping can be directed towards rear, 
right, downward, left or left-rear 
directions.

Rear side
Right

Rear

Downward

Left-rear

Left

Units should be installed by licensed contractor according 
to local code requirement.

PIPING PREPARATION

1

 Specifi cations

 

Use the refrigerant pipes that meet the following specifi cations.

Pipe

Outside diameter

Insulation thickness

Insulation material

mm

mm

For liquid

9.52

8

Heat resisting 
foam plastic 0.045 
specifi c gravity

For gas

15.88

8

  Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm 

(for ø6.35, 9.52) or 1.0 mm (for ø15.88). Never use any pipe with a thickness less 
than 0.8 mm (for ø6.35, 9.52) or 1.0 mm (for ø15.88), as the pressure resistance 
is insuffi cient. 

2

  Ensure that the 2 refrigerant pipes are insulated to prevent condensation.

3

  Refrigerant pipe bending radius must be 100 mm or more.

Air outlet

4-10 mm 

×

 21 mm slot

840 mm

330 mm

360 mm

500 mm

169 mm

15 mm

17 mm

10.5 mm

3.  INSTALLATION DIAGRAM & ACCESSORIES

FLARED CONNECTIONS

  This unit has fl ared connections on both indoor and outdoor sides.

  Remove the outdoor units valve cover, then connect the pipe.

  Refrigerant pipes are used to connect the indoor and outdoor units.

  Be careful not to crush or bend the pipe in pipe bending.

Limits

MS(H)-GD80

Pipe length

30 m max.

Height difference

15 m max.

No. of bends

10 max.

  Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant 

 

(R-410A) charge is required.

 

(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)

Pipe length

Up to 7 m

No additional charge is required.

Exceeding 7 m

Additional charge is required.
(Refer to the table below.)

Refrigerant to 
be added

MS-GD80

55 g/m × (refrigerant piping length (m) -7)

MSH-GD80

55 g/m × (refrigerant piping length (m) -7)

Note:

When operating the air conditioner in low outside temperature,
be sure to follow the instructions described below.

  Never install the outdoor unit in a place where its air inlet/outlet

  side may be exposed directly to wind.

 To prevent exposure to wind, install the outdoor unit with its 

  air inlet side facing the wall.

 To prevent exposure to wind, it is recommended to install a 

 baffl e board on the air outlet side of the outdoor unit.

ACCESSORIES

Check the following parts before installation.
<Indoor unit>

1

Installation plate

1

2

Installation plate fi xing screw 4 

×

 25 mm

7

3

Remote controller holder

1

4

Fixing screw for 

3

 3.5 

×

 16 mm (Black)

2

5

Battery (AAA) for remote controller

2

6

Wireless remote controller

1

7

Felt tape (Used for left or left-rear piping)

1

<Outdoor unit: MUH type>

8

Drain socket

1

9

Drain cap ø33

2

PART TO BE PROVIDED AT YOUR SITE

Optional extension pipe

A

Indoor/outdoor unit connecting wire
(2-core 1.0 mm

2

-2.0 mm

2

)

1

B

Extension pipe

1

C

Wall hole sleeve

1

D

Wall hole cover

1

E

Pipe fi xing band (The quantity depends  
on the pipe length.)

2 to 5

F

Fixing screw for 

E

 4 

×

 20 mm (The quan-

tity depends on the pipe length.)

2 to 5

G

Piping tape

1

H

Putty

1

I

Drain hose (or soft PVC. hose, 15 mm 
inner dia. or hard PVC pipe VP16)

1

J

Refrigeration oil

1

K

Power supply cord (See the table in 5
INDOOR/OUTDOOR WIRE CONNECTION
AND OUTDOOR POWER SUPPLY CORD
CONNECTION for the cord size.)

1

 CAUTION

Be sure to use the insulation of specifi ed thickness. Excessive thickness may 
cause incorrect installation of the indoor unit and lack of thickness may cause 
dew drippage.

Содержание MS-GD80VB

Страница 1: ...such as air can cause abnormal pressure rise or an explosion Q Earth the unit Do not connect the earth to a gas pipe water pipe lightning rod or telephone earth Defective earthing could cause an electric shock CAUTION Q Do not install the unit in a place where an inflammable gas leaks If gas leak and accumulate in the area surrounding the unit it could cause an explosion Q Install an earth leakage ...

Страница 2: ...ndoor and outdoor units Be careful not to crush or bend the pipe in pipe bending Limits MS H GD80 Pipe length 30 m max Height difference 15 m max No of bends 10 max Refrigerant adjustment If pipe length exceeds 7 m additional refrigerant R 410A charge is required The outdoor unit is charged with refrigerant for pipe length up to 7 m Pipe length Up to 7 m No additional charge is required Exceeding ...

Страница 3: ...e front panel 2 Remove one screw holding the electrical cover then remove the cover 3 Remove the VA clamp and the cord clamp 4 Pass the indoor outdoor unit connecting wire from the back of the indoor unit and process the end of the wire then connect it to the terminal block 5 Replace the fixture and electrical cover securely Indoor terminal block ELECTRICAL COVER Fixing screws Securely push the wir...

Страница 4: ...ain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtainable at a store around it Wrap the felt tape 7 around the pipe and the drain hose then put the pipe in the back space of the indoor unit Drain hose Be careful drain hose is not heaved Cut off in case of right piping Cut off in case of downward piping...

Страница 5: ...ose should point downward for easy drain flow Fig 1 Do not make drain piping as shown in Fig 2 to 5 INDOOR UNIT INSTALLATION Insert the drain hose into the wall hole sleeve C and hook the upper part of indoor unit on the installation plate 1 Then move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit After that cut the part of packing mate...

Страница 6: ...R410Ahas high pressures beyond the measurement range of existing gauges Port diameters have been changed to prevent any other refrigerant from being charged into the unit Charge hose No Hose material and cap size have been changed to improve the pressure resistance Gas leak detector No Dedicated for HFC refrigerant Torque wrench Yes 1 4 No 1 2 and 5 8 Flare tool Yes Clamp bar hole has been enlarge...

Страница 7: ...rm test run in the following procedure 6 3 PIPE CONNECTION Note Fasten a flare nut with a torque wrench as specified in the table below When fastened too tight a flare nut may broken after a long period and cause a leakage of refrigerant 1 Indoor unit connection Connect both liquid and gas pipings to indoor unit Apply a thin coat of refrigeration oil J on the seat surface of pipe For connection first ...

Страница 8: ...the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam 1 Remove the screw caps 2 Remove three screws 3 Pull the bottom Hold this concave section and pull the bottom forward to remove the front panel 4 Release the hooks Push Go down Square hole 5 Push Horizontal vane 3 2 4 1Point the horizontal vane slightly downward Union Indoor unit Liquid pipe Gas pipe St...

Страница 9: ...nks Model Number MS GD80VB MS GD80_Instruction_Book_ JG79A086H01 MS GD80_Declaration_of_Conformity_ CE2010B01 MS GD80_Installation_Manual_ JG79A087H01 MS GD80_Parts_Catalog_ OBB511 MS GD80_Service_Manual_ OBH511A ...

Отзывы: