15
MS-GA50VB
MS-GA60VB
MS-GA80VB
Part name
Figure
Check method and criterion
Indoor fan motor(MF)
MS-GA50/GA60VB
INNER FUSE
145
:
CUT OFF
MS-GA80VB
INNER
PROTECTOR
135
i
5
:
OPEN
Color of
lead wire
WHT – BLK
BLK – RED
MS-GA50/GA60VB
282
"
~ 305
"
141
"
~ 152
"
Measure the resistance with a tester.
(Part temperature 10˚C ~ 30˚C)
Refer to 9-6."Test point diagram and voltage",
"Indoor electronic control P.C. board", for the chart of thermistor.
Room temperature
thermistor(RT11)
Indoor coil thermistor
(RT12(main), RT13(sub))
Horizontal vane
motor(MV1)
Vertical vane
motor(MV2)
Motor par
t
Sensor par
t
Measure the resistance between the terminals with a tester.
(Part temperature 10˚C ~ 30˚C)
Color of lead wire
BRN – YLW
YLW – GRY
Normal
4.5 ~ 5.5V
Measure the voltage power ON.
(When fan revolved one time)
0V
➔
5V
➔
0V
(Approx.)
Normal
282
"
~ 306
"
Measure the resistance between the terminal with a tester.
(Part temperature 10
°
C ~ 30
°
C)
BLK
RED
WHT
GR
Y
YL
W
BRN
MAIN
AUX
FUSE
BLK
RED
WHT
GR
Y
YL
W
BRN
MS-GA80VB
133
"
~ 144
"
152
"
~ 165
"
Normal
MS-GA50/GA60VB
MS-GA80VB
YLW
GRN
ORN
BRN
RED
ROTOR
MAIN
AUX.
P
:INNER PROTECTOR
P
9-4. Trouble criterion of main parts
OB369D.qxp 12.1.13 8:47 AM Page 15
OB369D