10
SERVICE FUNCTIONS
7
MS-A18VD
MS-A24VD
MS-A30VD
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows. (Refer to 8-6.)
Set time : 1-minute
➔
1-second
Set time : 3-minute
➔
3-second
It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short
circuit of JPG and JPS.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
NOTE : For modification, take out the
batteries and press the
OPERATE/STOP(ON/OFF)
button twice or 3 times at first.
After finish modification, put
back the batteries then press
the RESET button.
Remote controller model : KP0B
Remote controller model : KM04B
J2
J1
J2
J1