![Mitsubishi Electric Mr. Slim SUZ-SA71VA Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-suz-sa71va/mr-slim-suz-sa71va_technical-and-service-manual_1811718022.webp)
22
23
11-4. TROUBLE CRITERION OF MAIN PARTS
Parts name
Figure
Check method and criterion
Outdoor fan motor
R.V. coil (21S4)
Expansion valve coil
(LEV)
Measure the resistance between terminals with a tester.
(Temperature: -10°C to 40°C)
WHT - BLK
BLK - RED
RED - WHT
Normal
Measure the resistance between terminals with a tester.
(Temperature : -10°C to 40°C)
Normal
Measure the resistance with a tester.
Refer to “11-6. Test point diagram and voltage” for the chart of thermistor.
Color of the lead wire
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to “11-6. Test point diagram and voltage” for the chart of thermistor.
Defrost thermistor (RT61)
Fin temperature
thermistor (RT64)
Measure the resistance between terminals with a tester.
(Temperature: -10°C to 40°C)
Compressor
U-V
U-W
V-W
Normal
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor(RT68)
1.19 k
Ω
to 1.78 k
Ω
0.92
Ω
to 1.12
Ω
12
Ω
to 17
Ω
LEV
WHT
RED
YLW
ORN
BLU
Measure the resistance with a tester.
(Temperature : - 10°C to 40°C)
RED - ORN
RED - WHT
RED - BLU
RED - YLW
Normal
37
Ω
to 54
Ω
Color of the lead wire
SUZ-SA71VA.TH
OCH561
Содержание Mr. Slim SUZ-SA71VA
Страница 11: ...11 7 WIRING DIAGRAM SUZ SA71VA TH OCH561 ...