15
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
MAX. REFRIGERANT PIPING LENGTH
Max. Length
A
* Height difference limitations are binding regardless of the height position at which either indoor or outdoor is placed higher.
* Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
Calculation : Xg=20g/m×(Refrigerant piping length(m)−7)
Calculation : Xg=55g/m×(Refrigerant piping length(m)−7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
11 m
12 m
13 m
14 m
15 m
20 m
SUZ-KA25VA5
800
0
30
60
90
120
150
180
210
240
390
SUZ-KA35VA5
1,150
0
30
60
90
120
150
180
210
240
390
Calculation: Xg=30g/m×(Refrigerant piping length(m)−7)
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
SUZ-KA25VA5
20
12
9.52
6.35
SUZ-KA35VA5
SUZ-KA50VA5
30
30
12.7
SUZ-KA60VA5
15.88
SUZ-KA71VA5
9.52
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
SUZ-KA50VA5
1,600
0
60
160
260
360
460
SUZ-KA60VA5
1,600
0
60
160
260
360
460
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
SUZ-KA71VA5
1,800
0
165
440
715
990
1,265
Pumping Down
When relocating or disposing of the air conditioner, pump down the system by following the procedure below so that no
refrigerant is released into the atmosphere.
1
Turn off the power supply (circuit breaker).
2
Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3
Fully close the stop valve on the liquid pipe side of the outdoor unit.
4
Supply power (circuit breaker).
5
Perform the refrigerant collecting operation (cooling test run).
• For the PAR-31MAA, select “Service” → “TestRun” from the main menu to start the test run, and then select the cooling mode.
• For details or for other information about starting the test run when using remote controllers, refer to the installation manual
for the indoor unit or the remote controller.
6
Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge]
(approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner.
• Push the “ON/OFF” button on the remote controller to stop the air conditioner.
Note:
When the extension piping is very long with a large refrigerant amount, it may not be possible to perform a pump down
operation. In this case, use refrigerant recovery equipment to collect all of the refrigerant in the system.
7
Turn off the power supply (circuit breaker), remove the gauge manifold valve, and then disconnect the refrigerant pipes.
.
Warning: When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open,
the pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst,
personal injury, etc.
OCH603