Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M
.
Turn on the main power to the unit.
Press the
TEST RUN
button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
A
TEST RUN
and current operation mode are displayed.
Press the
MODE
(
) button to activate
COOL
mode, then
check whether cool air is blown out from the unit.
Press the
MODE
(
) button to activate
HEAT
mode, then
check whether warm air is blown out from the unit.
Press the
FAN
button and check whether strong air is blown out
from the unit.
Press the
VANE
button and check whether the auto vane operates
properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps
to
.