![Mitsubishi Electric Mr.Slim PUHZ-RP100YKA Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-puhz-rp100yka/mr-slim-puhz-rp100yka_service-manual_1810290092.webp)
92
SW2 setting
Display detail
Explanation for display
Unit
:
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
Sub cool on error occurring SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
Thermo-on time until error stops
0~999
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
Indoor pipe temperature / Liquid
(TH2 (3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
50
1
:
1
ON
2 3 4 5 6
Discharge superheat on error occurring
SHd
0~255
Cooling = TH4-TH6
Heating = TH4-TH5
Indoor pipe temperature / Liquid
(TH2 (4))
Indoor 4
-39~88
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
Minute
:
:
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
15
1
15
4
1
ON
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva
(TH5 (4))
Indoor 4
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
: