background image

90

op

0.5

o

øA

R0.4~R0.8

45

op

 2

o

6

4.2. Connecting pipes (Fig. 4-1)

•  

When commercially available copper pipes are used, wrap liquid and gas pipes 
with commercially available insulation materials (heat-resistant to 100 °C or 
more, thickness of 12 mm or more).

•  

The indoor parts of the drain pipe should be wrapped with polyethylene foam 
insulation materials (specifi c gravity of 0.03, thickness of 9 mm or more).

•  

Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-
ing fl are nut. 

A

•  

Use two wrenches to tighten piping connections. 

B

•  

Use leak detector or soapy water to check for gas leaks after connections are 
completed.

•  

Apply refrigerating machine oil over the entire fl are seat surface. 

C

•  

Use the fl are nuts for the following pipe size. 

D

Gas side

Pipe size (mm)

[

15.88

Liquid side

Pipe size (mm)

[

9.52

•  

When bending the pipes, be careful not to break them. Bend radii of 100 mm to 
150 mm are suffi cient.

•  

Make sure the pipes do not contact the compressor. Abnormal noise or vibration 
may result.

1

 Pipes must be connected starting from the indoor unit.

 

Flare nuts must be tightened with a torque wrench.

2

  Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site).

•  

When usual pipe sealing is used, refer to Table 1 for fl aring of R410A refrigerant 
pipes.

 

The size adjustment gauge can be used to confi rm A measurements.

A

 (Fig. 4-1)

Copper pipe O.D.

(mm)

Flare dimensions

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

ø19.05

23.6 - 24.0

B

 (Fig. 4-1)

Copper pipe O.D. 

(mm)

Flare nut O.D. 

(mm)

Tightening torque 

(N·m)

ø6.35

17

14 - 18

ø6.35

22

34 - 42

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø12.7

29

68 - 82

ø15.88

29

68 - 82

ø19.05

36

100 - 120

A

 Flare cutting dimensions

B

 Flare nut tightening torque

A

B

C

D

A

 Die

B

 Copper pipe

A

B

Fig. 4-1

Fig. 4-2

A

Table 1 (Fig. 4-2)

Copper pipe O.D. 

(mm)

A (mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4")

0 - 0.5

1.0 - 1.5

ø9.52 (3/8")

0 - 0.5

1.0 - 1.5

ø12.7 (1/2")

0 - 0.5

1.0 - 1.5

ø15.88 (5/8")

0 - 0.5

1.0 - 1.5

ø19.05 (3/4")

0 - 0.5

1.0 - 1.5

4. Installing the refrigerant piping

Fig. 4-3

Front piping cover

Piping cover

Stop valve

Service panel

Bend radius : 100mm - 150mm

4.3. Refrigerant piping (Fig. 4-3)

Remove the service panel 

D

 (3 screws) and the front piping cover 

A

 (2 screws) 

and rear piping cover 

B

 (2 screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit, and the cyl-

inder/outdoor unit or hydrobox/outdoor unit when the outdoor unit’s stop valves 
are completely closed.

2

  Vacuum-purge air from the indoor unit, and the cylinder unit or hydrobox, and 

the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes, the indoor 

unit, and the cylinder unit or hydrobox, for gas leaks. (Refer to 4.4 Refrigerant 
pipe airtight testing method)

4

  A high-performance vacuum pump should be used at the stop valve service port 

to maintain a vacuum for an adequate time (at least one hour after reaching –
101 kPa (5 Torr)) in order to vacuum dry the inside of the pipes. Always check 
the degree of vacuum at the gauge manifold. If there is any moisture left in the 
pipe, the degree of vacuum is sometimes not reached with short-time vacuum 
application. 

 

 After vacuum drying, completely open the stop valves (both 2 sets of liquid and 
gas) for the outdoor unit. This completely links the refrigerant circuits in the in-
door unit, the cylinder unit or hydrobox, and the outdoor unit.

 •  If the vacuum drying is inadequate, air and water vapor remain in the refriger-

ant circuits and can cause abnormal rise of high pressure, abnormal drop of 
low pressure, deterioration of the refrigerating machine oil due to moisture, etc.

 •  

If the stop valves are left closed and the unit is operated, the compressor and 
control valves will be damaged.

 •  

Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.

 •  

Do not use the refrigerant from the unit to purge air from the refrigerant lines.

 •  

After the valve work is completed, tighten the valve caps to the correct torque: 
20 to 25 N·m (200 to 250 kgf·cm).

 

 

 Failure to replace and tighten the caps may result in refrigerant leakage. In 
addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

  Use sealant to seal the ends of the thermal insulation around the pipe connec-

tion sections to prevent water from entering the thermal insulation.

A

B

WIRING WORK:  Connect to power and 

indoor unit

WIRING WORK:  Connect to cylinder unit or 

hydrobox

PIPING WORK:  Connect to cylinder unit or 

hydrobox

PIPING WORK:  Connect to indoor unit

E

D

C

A

B

C

D

This tap mark indicates the cylinder/hydro 
unit connection side for the following parts.
 •  

Terminal block for the connecting 
cables, S1/S2/S3

 •  

Stop valves, gas and liquid for the 
refrigerant connection

Содержание Mr.Slim PUHZ-FRP71VHA

Страница 1: ...anuale ed il manuale d installazione dell unità interna prima di installare l unità esterna Il testo originale è redatto in lingua Inglese Le altre versioni linguistiche rappresentano traduzioni dell originale MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar o aparelho de unidade exterior O idioma...

Страница 2: ... high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized ...

Страница 3: ...nt pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 2 Installation location Fig 2 1 2 1 Refrigerant pipe Fig 2 1 Check that the difference between the heights of the i...

Страница 4: ...ide In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 4 Obstacles at front and rear only Fig 2 15 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance should be 500 mm or more 6 Multiple parallel unit arrangement Fig 2 17 When using an optiona...

Страница 5: ...round Max 30 B A C E D 600 Min 360 600 Min 10 175 950 175 25 330 370 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipe...

Страница 6: ...2 screws 1 Perform refrigerant piping connections for the indoor outdoor unit and the cyl inder outdoor unit or hydrobox outdoor unit when the outdoor unit s stop valves are completely closed 2 Vacuum purge air from the indoor unit and the cylinder unit or hydrobox and the connection piping 3 After connecting the refrigerant pipes check the connected pipes the indoor unit and the cylinder unit or ...

Страница 7: ...ry if the total pipe length does not exceed 30 m If the total pipe length exceeds 30m charge the unit with additional R410A re frigerant according to the permitted pipe lengths in the chart shown on the right When the unit is stopped charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacuumized When the unit is operatin...

Страница 8: ...s are used for gas or oil heat pump systems use new pipes The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping Drain socket PAC SG61DS E Drain pan PAC SG64DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin indoor units combination ...

Страница 9: ...al code 2 Power supply cords the Indoor Outdoor connecting cable and the Cylinder or Hydrobox Outdoor connecting cable shall not be lighter than polychlo roprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied 6 Electrical work A Control Outdoor Unit S1 S2 S3 S1 S2 S3 3 poles isolato...

Страница 10: ...4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The linear expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of th...

Страница 11: ...ically in 5 minutes 6 Turn off the main power Warning Do not disconnect extension pipes during the refrigerant collecting operation is running If you open the stop valves to the air during the compressor is running the pressure could be abnormal high level and this may cause a rupture of the compressor or other hazardous situation Use a refrigerant recovery machinery if the refrigerant collecting ...

Страница 12: ...n omalla vastuullaan että seuraavassa kuvattavat asuinkiinteistöihin liikekiinteistöihin ja kevyen teollisuuden ympäristöihin tarkoitetut ilmastointilaitteet ja lämpö pumput MITSUBISHI ELECTRIC PUHZ FRP71VHA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve sur...

Страница 13: ...atterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging veroorzaken Installeer het apparaat op een stabiele structuur om overmatig lawaai of trillingen te voorkomen Het niveau van de geluidsdruk ligt onder 70 dB A Dit apparaat is bedoeld voor gebruik door ervaren of opgeleide gebruikers in werkplaatsen in de lichte industrie en op boerderijen of...

Страница 14: ...00 100 500 150 100 1000 300 Max 500 200 1000 300 1000 Max 300 1000 1000 300 500 400 1000 100 1000 400 2000 300 1000 500 150 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Страница 15: ...ET UXBRIDGE MIDDLESEX UB8 1QQ U K This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC RoHs Directive 2011 65 EU ...

Отзывы: