![Mitsubishi Electric Mr.SLIM PSA-RP100KA Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-psa-rp100ka/mr-slim-psa-rp100ka_service-manual_1810263021.webp)
CN90
Connect to the wireless
remote controller board
(CNB)
CN20
Room temperature
thermistor (TH1)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
LED3
Transmission
(Indoor/outdoor)
CN44
Pipe temperature
thermistor
1
-
2
: Liquid (TH2)
3
-
4
: Cond./Eva. (TH5)
CN105
21
Indoor controller board
PSA-RP71KA
PSA-RP100KA
PSA-RP125KA
PSA-RP140KA
9-5. TEST POINT DIAGRAM
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN22
Remote controller connecting
wire(10.4~14.6V DC)
CNP
Louver motor output
(220-240V AC)
CN01
Connect to the Terminal Block
(TB4)
(Indoor/outdoor connecting line)
Between
3
and
5
220-240V AC
SWE
Emergency operation
Jumper wire J41,J42
Pair No. setting for wireless
remote controller
FUSE
6.3A /250V
CNMF
Fan motor
1
-
4
: DC 310~340V
5
-
4
: DC15V
V
SP
: Voltage between pins of
C626
DC0V (FAN stop)
DC1~6.5V (FAN operation)
(Same as
6
(+)–
4
(-) of CNMF)
V
FG
: Voltage between
PC6722 and C955(-)
(Same as
7
(+)–
4
(-) of CNMF)
V
CC
: Voltage between pins of
C955 15VDC
(Same as
5
(+)–
4
(-) of CNMF)
CN51
Centrally control
1
-
2
: Control signal
13V pulse input (
1
: +)
3
-
4
: Operation indicator
13VDC (
3
: +)
3
-
5
: Malfunction indicator
13VDC (
3
: +)
OCH528