28
9-5. EMERGENCY OPERATION
9-5-1. When wireless remote controller fails or its battery is exhausted
9-5-2. When wired remote controller or indoor unit microprocessor fails
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote control-
ler malfunctions, the emergency operation can be done using the emer-
gency buttons on the grille.
A
DEFROST/STAND BY lamp
B
Operation lamp
C
Emergency operation switch (fan mode)
D
Emergency operation switch (cooling)
E
Receiver
Starting operation
•
To operate the cooling mode, press the button
D
for more than 2
seconds.
•
To operate the fan mode, press the button
C
for more than 2
seconds.
* Lighting of the Operation lamp
B
means the start of operation.
Note:
•
Details of emergency mode are as shown below.
Operation mode
COOL
Set temperature
24 °C
Fan speed
High
Air flow direction
Horizontal
Stopping operation
• To stop operation, press the
button
D
or the button
C
.
C
D
A
B
E
1. When the wired remote control or the indoor unit microprocessor has failed, but all other components work properly,
if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin emergency operation.
When emergency operation is activated, the indoor unit operates as follows:
(1) Indoor fan is running at high speed. (2) Drain pump is operating.
Note on the wireless remote control: when the remote control does not function, it is possible to activate.
emergency operation by using the indoor unit emergency operation switch (SW1, SW2 of the wireless signal
receiver board).
However, if the indoor unit microprocessor has failed, it is necessary to proceed with points (2) and (3) below as in the
case of the wired remote controller.
2. Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the indoor fan malfunctions.
• when it has detected the malfunction of drain pump during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc. does not function.
(3) After emergency operation has been deactivated, set the switches etc. to their original positions.
(4) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.
OCH551A