22
Weight
kg (lbs.)
Service Ref.
Power supply (phase, cycle, voltage)
Running current
A
Starting current
A
External finish
Refrigerant control
Compressor
Model
Motor output
kW
Starter type
Protection devices
Heat exchanger
Fan (drive)
o
No.
Fan
Fan motor output
kW
Airflow
K
/ min (CFM)
Crankcase heater
W
Defrost method
Sound level
Service Ref.
Item
Function
Capacity
Btu/h
W
Total input
kW
Service Ref.
Power supply (phase, cycle,voltage)
Input
kW
Running current
A
Starting current
A
External finish (Panel)
Heat exchanger
Fan
Fan (drive)
o
No.
Fan motor output
kW
Airflow
(Low-Medium2-Medium1-High)
K
/ min (CFM)
External static pressure
Pa (mmAq)
Booster heater
kW
Operation control & Thermostat
Sound level
(Low-Medium2-Medium1-High)
dB
Unit drain pipe I.D.
mm (in.)
Dimensions
Indoor unit
W
mm (in.)
D
mm (in.)
H
mm (in.)
Dimensions
Outdoor unit
Refrigerant piping
Weight
kg (lbs.)
Refrigerant
Charge
kg (lbs.)
Oil (Model)
L
Pipe size O.D.
Cooling
43,700
48,000
12,800
14,300
5.00
5.94
PLA-P5AA
1
.UK
PLA-P6AA
1
.UK
PLA-P5AA.UK
PLA-P6AA.UK
PLA-P5AA
1
.UK
PLA-P6AA
1
.UK
PLA-P5AA.UK
PLA-P6AA.UK
Single phase, 50Hz, 220-230-240V
0.30
0.34
1.43
1.64
2.0
2.0
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct)
o
1
0.120
22-25-28-30 (775-880-990-1,060)
0 (direct blow)
—
Remote controller & built-in
35-38-41-43
37-40-43-45
32 (1-1/4)
UNIT : 840 (33-1/16), PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16), PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4), PANEL : 30 (1-3/16)
UNIT : 30 (66), PANEL : 5 (11)
UNIT : 32 (71), PANEL : 5 (11)
PU-P5YGAA.UK
PU-P6YGAA.UK
3 phase, 50Hz, 380-400-415V (4wires)
7.60
9.03
65.5
74
Munsell 5Y 7/1
Linear expansion valve
Hermetic
ZR61KCE-TFD
ZR72KCE-TFD
3.5
4.2
Line start
Internal thermostat,Thermal relay, HP switch, Discharge thermo.
Plate fin coil
Propeller (direct)
o
2
0.070+0.070
95 (3,360)
100 (3,530)
38
—
55
57
1,050 (41-5/16)
330+20 (13+3/4)
1,260 (49-5/8)
122 (269)
R407C
4.6 (10.1)
1.690 (Ester)MMM-POE
4.9 (10.8)
1.774 (Ester)MMM-POE
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
Liquid
mm (in.)
Gas
mm (in.)
Connection method
Indoor side
Outdoor side
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor : D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor: D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
3. Above data based on indicated voltage
Indoor unit
Single phase 240V 50Hz
Outdoor unit
3 phase 415V 50Hz
Between the indoor &
outdoor units
Height difference
Piping length
Cooling
dB
W
mm (in.)
D
mm (in.)
H
mm (in.)