OC246-37
4. How to check the parts PL12AK/PL18AK/PL24AK/PL30AK/PL36AK/PL42AK
Parts name
Check points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 50
-
F~86
-
F)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 68
-
F~86
-
F)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 68
-
F~86
-
F)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 50
-
F~86
-
F)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature
thermistor (RT1)
Liquid pipe
thermistor (RT2)
1
2
Yellow
Yellow
1
2
3
Normal
4.3k
"
~9.6k
"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k
"
~6.0k
"
Normal
Connector
Abnormal
300
"
Open or short
Normal
Abnormal
101
"
Open or short
Orange
Red
White
Red Ñ Yellow
Red Ñ Blue
Red Ñ Orange
Red Ñ White
Blue
Yellow
3
5
1
2
4
Measure the resistance between the terminals using a tester.
Fan motor
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
12/18AK
21.7
"
26.5
"
Abnormal
Open or short
24/36/42AK
8.5
"
12.2
"
Red-Black
White-Black
Motor terminal
or
Relay connector
Normal
PL