background image

13

4. STANDARD OPERATION DATA

Models

Item

Electrical circuit

Refrigerant circuit

Indoor side

Outdoor side

Voltage

Frequency

Total input

Indoor fan current 

Booster heater current

Outdoor fan current 

Comp. current

Condensing pressure

Suction pressure

Discharge temperature

Condensing temperature

Suction temperature

Comp.shell bottom temperature

Ref. pipe length

Refrigerant charge

Fan speed

Airflow (High)

Fan speed upper/lower

Airflow

Unit

V

Hz

kW

A

A

A

A

psi.G

psi.G

˚F

˚F

˚F

˚F

ft

˚F

˚F

˚F

˚F

r.p.m.

CFM

˚F

˚F

r.p.m.

CFM

Btu/h

208/230

1.79

0.5

0.75

7.4/6.9

255

81

182

118

66

171

80

67

61

59

95

75

18,000

0.82

60

Cooling

208/230

1.56

0.5

7.6/8.4

0.75

6.1/5.9

202

61

126

102

34

111

70

60

96

68

47

43

18,600

Heating

PKH18FL

208/230

2.36

0.5

0.65+0.65

9.3/8.7

240

75

158

115

46

141

80

67

58

56

95

75

24,000

0.71

60

Cooling

208/230

2.37

0.5

7.6/8.4

0.65+0.65

9.5/8.7

243

63

149

115

35

126

70

60

105

70

47

43

25,000

Heating

PKH24FL

208/230

3.12

0.6

0.75+0.75

12.6/11.8

245

80

158

115

49

138

80

67

59

58

95

75

30,000

0.75

60

Cooling

208/230

3.02

0.6

8.7/9.6

0.75+0.75

12.2/11.4

236

60

159

113

32

130

70

60

103

70

47

43

33,000

Heating

PKH30FL

208/230

3.44

0.6

0.75+0.75

14.3/13.2

243

74

160

115

45

142

80

67

58

56

95

75

34,200

0.71

60

25 

5 lbs 8 oz

1,310

710

1,310

710

1,400

990

1,400 

990

790

1,590

750/750

3,170

760/760

3,350

760/760

3,350

25

9 lbs 15 oz

25

10 lbs 2 oz

25

10 lbs 9 oz

Cooling

208/230

3.54

0.6

8.7/9.6

0.75+0.75

14.7/13.7

263

60

170

120

33

148

70

60

109

71

47

43

38,000

Heating

PKH36FL

Intake
air temperature

Discharge
air temperature

Intake
air temperature

Capacity

SHF

DB

WB

DB

WB

DB

WB

OC276-A-1.qxp  03.11.25 9:04 AM  Page 13

Содержание Mr.Slim PKH18FL

Страница 1: ...ED EDITION A AIR STANDARD 240 M A N U F A C T U R E R CERTIFIED TO ARI AS CO M P L Y I N G W I T H C E RTIFICATION SECTIONS O F EQUIPMENT AIR CO N D I T I O N I N G U N I T A R Y LIST ED C US Wall Mounted Series PKH Models Indoor unit Remote controller MODEL SELECT NOT AVAILABLE SWING CHECK FAN TEST RUN F C AMPM STOP START Revision The wrong descriptions in REFRIGERANT SYSTEM DIAGRAM have been mod...

Страница 2: ...and refrigerant piping radically improves flexibility in selecting installation layouts PKH18 24 30 36FL models boast refrigerant piping in 4 directions and drain piping in 2 directions 2 Back plate installation guide The back plate installation guide gives clear instructions on installation positions The enlarged back plate secures the unit firmly to the wall while the support piece which lifts t...

Страница 3: ... button SET TEMPERATURE button sets any desired room temperature CLOCK display Displays the current time display Displays the order of timer operation display Displays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons 88 F display SET TEMP display indicates desired temper ature set display FAN SPEED display indicates which f...

Страница 4: ...6 0 65 0 65 NH33NBD 11 5 54 0 16 0 17 33 39 Capillary tube Reverse cycle 55 49 9 16 202 With indoor unit Indoor unit remote controller DC12V Indoor unit outdoor unit DC12V R22 9 lbs 15 oz 1 2 MS32N 1 Not supplied optional parts Flared Flared 9 1 4 13 3 8 PKH30FL 30 000 33 000 39 100 40 500 19 000 25 100 26 500 9 1 3 12 3 02 4 82 5 22 2 48 4 28 4 68 9 6 10 6 7 1 3 2 2 2 PKH30FL FK1 49 44 66 PUH30EK...

Страница 5: ...0 15 2 13 6 13 1 12 6 14 2 16 3 18 0 15 8 15 4 14 9 19 0 21 5 23 5 20 7 20 1 19 4 20 2 23 1 25 6 22 5 21 8 21 0 TPC 1 99 1 93 1 88 1 87 1 84 1 83 2 63 2 55 2 47 2 47 2 41 2 39 3 48 3 37 3 27 3 26 3 21 3 19 3 83 3 71 3 61 3 59 3 52 3 50 TC 17 6 16 3 15 1 15 0 14 2 13 9 23 4 21 7 20 1 19 9 18 9 18 5 29 3 27 1 25 1 24 9 23 5 22 9 33 4 30 9 28 7 28 4 26 9 26 4 SHC 12 1 13 4 14 4 12 9 12 4 12 0 13 5 15...

Страница 6: ... 5 32 8 33 3 33 9 43 2 43 7 44 6 49 6 50 4 51 3 PC 1 99 1 91 1 83 3 01 2 90 2 78 3 86 3 72 3 56 4 49 4 28 4 14 CA 5 5 6 5 5 5 6 5 6 1 7 5 6 1 7 5 PC 1 6 1 9 1 6 1 9 1 8 2 2 1 8 2 2 IWB F 15 25 35 45 55 65 Auxiliary heater 208V 230V 710 710 990 990 Airflow CFM PKH24FL PKH30FL PKH36FL Notes 1 IDB Intake air dry bulb temperature CA Capacity x103 Btu h PC Power Consumption kW 2 When booster heater is ...

Страница 7: ...rature F 65 65 70 70 75 75 2 PERFORMANCE CURVE NOTES A point on the curve shows the reference point COOLING CAPACITY HEATING CAPACITY COOLING CAPACITY HEATING CAPACITY Does not include booster heater 1 9kW Total power consumption kW Total capacity x10 3 Btu h 30 24 18 12 2 5 2 0 1 5 1 0 15 25 35 45 55 65 Total power consumption kW Total capacity x10 3 Btu h Outdoor intake air DB temperature F Outd...

Страница 8: ...erature F indoor intake air DB temperature F Does not include booster heater 2 2kW 65 70 75 75 70 65 Total capacity x10 Btu h 3 Total power consumption kW 42 36 30 24 4 5 4 0 3 5 3 0 2 5 Total capacity x10 Btu h 3 indoor intake air WB temperature F SHF 0 71 Total power consumption kW Outdoor intake air DB temperature F indoor intake air WB temperature F 0 23 32 35 45 55 65 67 75 85 95 105 115 71 6...

Страница 9: ...00 110 Outdoor ambient temperature DB F Indoor DB temperature F 86 80 75 70 100 90 80 70 60 50 40 30 20 psi G Suction pressure 30 40 50 60 70 80 90 100 110 Outdoor ambient temperature DB F 86 80 75 70 Indoor DB temperature F 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 psi G Condensing pressure 30 35 20 25 45 55 65 40 50 60 70 Outdoor ambient temperature DB F...

Страница 10: ...ature DB F Indoor DB temperature F 86 80 75 70 100 90 80 70 60 50 40 30 20 psi G Suction pressure 30 40 50 60 70 80 90 100 110 Outdoor ambient temperature DB F 86 80 75 70 Indoor DB temperature F 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 psi G Condensing pressure 30 35 20 25 45 55 65 40 50 60 70 Outdoor ambient temperature DB F 75 70 65 Indoor DB tem perat...

Страница 11: ...ature DB F 86 80 75 70 110 100 90 80 70 60 50 40 30 psi G Suction pressure 30 40 50 60 70 80 90 100 110 Outdoor ambient temperature DB F 86 80 75 70 Indoor DB temperature F Indoor DB temperature F 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 140 psi G Condensing pressure 30 35 20 25 45 55 65 40 50 60 70 Outdoor ambient temperature DB F 75 70 65 Indoor DB tem pera...

Страница 12: ...erature DB F 86 80 75 70 90 80 70 60 50 40 30 20 psi G Suction pressure 30 40 50 60 70 80 90 100 110 Outdoor ambient temperature DB F 86 80 75 70 Indoor DB temperature F Indoor DB temperature F 390 380 370 360 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 psi G Condensing pressure 30 35 20 25 45 55 65 40 50 60 70 Outdoor ambient temperature DB F 75 70 65 Indoor DB tem peratur...

Страница 13: ...Heating PKH18FL 208 230 2 36 0 5 0 65 0 65 9 3 8 7 240 75 158 115 46 141 80 67 58 56 95 75 24 000 0 71 60 Cooling 208 230 2 37 0 5 7 6 8 4 0 65 0 65 9 5 8 7 243 63 149 115 35 126 70 60 105 70 47 43 25 000 Heating PKH24FL 208 230 3 12 0 6 0 75 0 75 12 6 11 8 245 80 158 115 49 138 80 67 59 58 95 75 30 000 0 75 60 Cooling 208 230 3 02 0 6 8 7 9 6 0 75 0 75 12 2 11 4 236 60 159 113 32 130 70 60 103 70...

Страница 14: ... 5 130ft 4 4 10 10 150ft 7 16 16 164ft 9 20 20 Refrigerant piping length one way 5 lbs 8 oz 9 lbs 15 oz 10 lbs 2 oz 10 lbs 9 oz PKH18FL PKH18FL PKH24FL PKH30FL PKH36FL PKH24FL PKH30FL PKH36FL With wind baffle D B 23 F if no wind baffle 5 OPERATING RANGE 1 POWER SUPPLY 6 OUTLET AIR SPEED AND COVERAGE RANGE 7 ADDITIONAL REFRIGERANT CHARGE R22 oz 1 Phase 60Hz 208 230V Guaranteed voltage range 2 OPERA...

Страница 15: ...AND CENTER FREQUENCIES Hz Hi NOTCH Lo 49 SPL dB 44 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR BAND CENTER FREQUENCIES Hz Hi NOTCH Lo 48 SPL dB 41 LINE Wall Unit 3 3ft 3 3ft Ambient temperature 80 F Test conditions are based on JIS...

Страница 16: ... 15 32 2 29 32 5 32 1 5 32 11 1 32 1 3 16 7 1 4 1 3 16 3 5 32 1 3 18 2 3 8 13 32 1 17 32 1 15 32 2 9 16 3 15 16 A B C Knock out hole for piping 31 32 43 11 16 7 7 32 9 7 16 B 44 3 32 21 23 32 4 23 32 2 5 32 4 7 32 4 3 8 Air outlet 21 23 32 Air outlet Change vane manual Under panel Removable at left hand side piping Knock out hole for under piping Refrigerant pipe Drain pipe Rear piping opening Ran...

Страница 17: ... side Air intake 5 15 16 or less 1 3 16 or more 10 or more Air outlet 13 3 8 Knock out hole for left piping 1 3 16 1 3 16 1 15 32 1 15 32 2 9 16 1 15 32 1 17 32 1 17 32 3 15 16 3 15 16 5 32 5 32 2 29 32 2 29 32 2 9 16 3 27 32 1 17 32 Lower side 2 1 Knock out hole for wiring 2 or more 10 or more 9 1 4 1 25 32 9 1 4 1 25 32 9 1 4 1 25 32 9 1 4 1 2 1 25 32 2 15 32 1 2 11 5 8 23 32 Wall fixture Unit o...

Страница 18: ... tube 0 157x 0 07x19 7 was wrong PKH30FL 0 157x 0 079x23 6 PKH36FL 0 157x 0 079x15 7 Pipe temperature thermistor Liquid RT2 Distributor Restrictor valve Capillary tube Refrigerant pipe option 1 2 with heat insulator Refrigerant pipe option 3 4 with heat insulator Strainer Flared connection Flared connection PKH18FL PKH24FL PKH30FL PKH36FL 6 REFRIGERANT SYSTEM DIAGRAM COOLING HEATING Refrigerant fl...

Страница 19: ...lock 5 Emergency operation If remote controller or microcomputer fails but there is no other trouble emergency operation is possible by setting dip switch SW3 I B on the indoor controller board Check items 1 Make sure that no other trouble exist in the outdoor unit Trouble with the outdoor unit prevents emergency operation 2 Make sure that there is no trouble with the indoor fan Emergency operatio...

Страница 20: ...P Auxiliary heater OFF Compressor OFF Fan STOP Four way valve OFF MAIN OPERATION w1 In addition the centralised control and remote control can be operated w2 The modes which indicate the sources of trouble are listed below E0 Signal transmitting receiving error P1 Room temperature thermistor malfunction P2 Indoor coil thermistor malfunction P4 Drain sensor malfunction P5 Drain overflow P6 Coil fro...

Страница 21: ...g protection detection temperature 30 F or lower YES NO 6 minute time delay 3 minute time delay Coil frost prevention release Allowance period 6 minute time delay Allowance set 1 min continue Coil frost protection FAN speed LOW FAN speed LOW 5 min elapse Outdoor unit trouble COOLING OPERATION w8 When operation stops or changes to cooling or dry mode the auto vane turns to a horizontal angle If ope...

Страница 22: ...ipe temperature is below 43 F the fan speed changes to LOW mode It is not possible to set the fan speed with the remote controller DRY OPERATION DRY operation Four way valve OFF Initial dry operation Room temperature is 64 F or lower During compressor ON Compressor thermostat ON Vane initial setting Vane setting notch 10 minute compressor OFF timer start Compressor OFF Fan STOP 3 minute time delay...

Страница 23: ...owance set Compressor OFF Indoor piping 95 F or higher HOT adjust 5 min elapse FAN SPEED Low FAN SPEED Low 2 min elapse FAN SPEED setting notch Hot adjust release 3 minute Auxiliary heater OFF Indoor coil thermistor is 140 F or higher FAN speed Low notch Airflow 10 up FAN setting notch Auto COOL HEAT operation Initial mode T1 To COOL mode HEAT mode COOL mode T1 To 4 After 15min T1 To 4 COOL operat...

Страница 24: ...ART STOP Fan speed control Crankcase heater control ON OFF Self diagnostic function Independent Control of Outdoor Unit OUTPUT to indoor unit INPUT from indoor unit INPUT to remote controller Remote controller board Processes and transmits orders OUTPUT to remote controller Indoor controller board Receives orders from remote controller and tem perature data from indoor unit Processes orders and da...

Страница 25: ...ane Booster heater Compressor ON LOW or HIGH LOW or HIGH ON ON OFF OFF ON OFF OFF OFF OFF Operation starts by POWER b u t t o n ON Operation stops by POW ER button OFF Room temperature becomes equal to set temperature Room temperature rises above set temperature COOL operation time chart w1 Even if the room temperature rise above the set temperature during this period the compressor will not start...

Страница 26: ... has been continuously operated for 3 minutes or more and the indoor coil temperature has been 5 F or below for 3 minutes the coil frost protection will start Coil frost protection Compressor stops for 6 minutes and then restarts lf the start condition is satisfied again during the first 10 minutes of compressor operation both the indoor and outdoor units stop displaying a check code of P6 on the ...

Страница 27: ...d 4 SWING 5 Remote controller display Changes by pressing the AIR DISCHARGE button AUTO RETURN When discharge 60 or 70 continues for 1 hour with the fan speed at LOW the discharge direction turns to the horizontal discharge automatically After that 60 or 70 is available by setting with the remote controller and it continues for 1 hour If the discharge direction changes from 60 or 70 the direction ...

Страница 28: ...f the dif ference is still out of RANGE C the outdoor unit is functioning abnormally Thus the compressor stops and check code P8 appears on remote controller RANGE A Indoor coil temperature is more than 9 degrees above room temperature RANGE B Indoor coil temperature is within 9 degrees either way of room temperature RANGE C Indoor coil temperature is more than 9 degrees below room temperature Ind...

Страница 29: ...ve set temperature w1 Even if the room temperature rises above the set temperature during this period the compressor will not start until this period has ended 2 2 DRY operation How to operate 1 Press POWER ON OFF button 2 Press the MODE button to display DRY 3 Press the TEMP or button to set the desired temperature NOTE The set temperature changes 2 F when the TEMP or button is pressed one time D...

Страница 30: ...th thermostat ON the compressor will operate for 2 more min utes and then stop for 3 minutes If the room temperature thermistor reads below 75 F with thermostat ON the compressor will stop for 3 minutes If the thermostat is OFF regardless of room temperature the compressor will stop for 10 minutes 5Coil frost protection Coil frost protection in DRY operation is the same as in COOL operation 6Coil ...

Страница 31: ...t temperature Room temperature falls below set tem perature w2 Even if the room temperature falls below the set temperature during this period the compressor will not start until this peri od has ended HEAT operation time chart How to operate 1 Press POWER ON OFF button 2 Press the MODE button to display HEAT 3 Press the TEMP or button to set the desired temperature NOTE The set temperature change...

Страница 32: ...stment is a warm up for HEAT operation Start conditions The hot adjustment works under any of the following conditions HEAT operation starts Defrosting ends Thermostat turns ON Hot adjustment Initially the indoor fan runs on LOW speed When 5 minutes have passed or the indoor coil temperature exceeds 95 F the fan speed will not be changed 2 minutes later the hot adjustment ends Then the fan speed d...

Страница 33: ...ure difference is still in RANGE C the outdoor unit is determined to be abnormal When RANGE B does not change to RANGE A after 20 minutes have passed since RANGE C had outdoor unit is determined to be abnormal iii During compressor OFF Not detecting abnormalities 6 Indoor coil temperature abnormality detection An abnormality can be detected during compressor ON except for the following For the fir...

Страница 34: ...outside air temperatures as follows Mode change HEAT COOL When room temperature becomes 4 degrees above the set temperature the operation mode can not be changed for 15 minutes degree To 4 To Set temperature 65 83 F To 2 To To 2 To 4 Compressor Start HEAT mode HEAT mode Mode change 15 minutes 15 minutes Minimum 3 minutes COOL mode COOL HEAT ON OFF 10 20 30 40 50 60 70 80 90 100 110 120 COOLING 0 F...

Страница 35: ...scharge the 1 hour timer to return the horizontal discharge is cancelled 2 HEAT operation At the start up of HEAT operation discharge direction depends on the setting of the last operation After it can be changed to another direction with VANE button The discharge direction shifts to 10 regardless of the remote controller settings under any of the following conditions Thermostat OFF Defrosting Ind...

Страница 36: ...d check that it is equal to or greater than 1 0M 1 Turn on the main power to the unit 2 Press the button twice continuously Start this operation from the status of remote controller display turned off A and current operation mode are displayed 3 Press the button to activate COOL mode then check whether cool air is blown out from the unit 4 Press the button and check whether strong air is blown out...

Страница 37: ...ation CAUTION When the self diagnostic function indicates a check code of P5 drain pump malfunction do not start the emergency operation because the drain may overflow How to operate 1 For emergency cooling set the dip switch SW3 1 to ON and SW3 2 to OFF For emergency heating set the dip switch SW3 1 2 to ON 2 Turn ON the outdoor unit breaker and then ON the indoor unit breaker Emergency operation...

Страница 38: ...from the actual living space temperature by about 7 degrees Therefore the room temperature read by room temperature thermistor must be lowered by 7 degrees OFF 7 degree adjustment ON NO adjustment SW1 5 Not for use SW1 6 Switch for fan speed during thermostat OFF in HEAT operation OFF LOW ON LOW or HIGH set with remote controller SW1 7 Switch for detecting abnormalities in the outdoor unit abnorma...

Страница 39: ... to set the output of phase controlled indoor fan motor Address setting is available at any time The initial factory setting by is based on each capacity Service Ref SW7 PKH30FL PKH36FL 1 2 3 ON OFF 1 2 3 ON OFF PKH24FL 1 2 3 ON OFF PKH18FL 1 2 3 ON OFF 7 SW8 Option SW8 1 2 Not for use SW8 3 4 Not for use SW8 5 Not for use SW8 6 OFF For 230V power supply ON For 208V power supply 1 2 3 4 ON OFF 5 6...

Страница 40: ... like Start this operation from the status of remote controller display turned off blinks and Model No is lighted 3 Press the button twice continuously A Pair No 0 blinks 4 Press the temp button to set the pair number you want to set 5 Press the SET button with the point of a ball point pen or the like Set pair number is lighted for three seconds then turned off MODELSELECT min A Pair No of wirele...

Страница 41: ...ver section and the number of blinks of the operation lamp 4 Press the ON OFF button to stop the self check CHECK h CHECK ON OFF TEMP FAN VANE MODE CHECK LOUVER TEST RUN AUTO STOP AUTO START h min RESET SET CLOCK 4 A B 3 2 1 2 3 4 5 6 7 8 9 Check Code Alarm Buzzer sound Suction sensor alarm Pipe sensor alarm Transmission alarm Drain sensor alarm Drain pump alarm Anti freezing on Anti overheat on S...

Страница 42: ...k the indoor outdoor connecting wire 2 Change the connection of electric wiring 3 Check the protection device 4 Measure the resistance of the outdoor coil ther mistor If the resistance is normal replace the outdoor controller board 1 2 Abnormality of room temper ature thermistor RT1 Abnormality of indoor coil thermistor RT2 1 Bad contact of thermistor 2 Damaged thermistor 1 Check the thermistor 2 ...

Страница 43: ...t stops ON Operation stops 9 minutes later check code P8 appears on remote controller display HEAT OFF Operation stops ON Operation stops 27 minutes later check code P8 appears on remote controller display Outdoor Indoor 1 2 3 1 2 3 COOL OFF Outdoor unit stops ON Operation stops 9 minutes later check code P8 appears on remote controller display HEAT OFF Operation stops ON Operation stops 27 minute...

Страница 44: ...0 30 40 50 4 14 32 50 68 86 104 122 Thermistor for lower temperature Temperature F Resistance K Thermistor Characteristic graph Room temperature thermistor RT1 Pipe temperature thermistor RT2 Thermistor R0 15k 3 Fixed number of B 3480k 2 Rt 15exp 3480 32 F 15k 50 F 9 6k 68 F 6 3k 77 F 5 4k 86 F 4 3k 104 F 3 0k Thermistor for lower temperature 1 273 t 1 273 30 36FL 62 6 i10 74 0 i10 Vane motor MV M...

Страница 45: ... the electrical box cover and remove the cover 3 Disconnect the connectors on the indoor controller board 4 To unhook the catches on the right hand side of the indoor controller board pull the left hand side toward you and lift up the cover to the right Then the indoor controller board can be removed 4 Removing the electrical box 1 Remove the right side panel 2 Remove the screw of the electrical b...

Страница 46: ...the catch on the panel from the catch on the unit 2 Slide the left side panel to the left to remove the panel Note Fix the unit to the metal fixture securely 3 Remove the air filters 4 Hold and press the center cover to remove 5 Remove the screws of the grilles 6 Pull the lower side of the grille toward you and slide the upper to the right to remove the grilles 7 Removing the drain pan 1 Remove th...

Страница 47: ...toward you and remove the line flow fan 9 Removing the electrical heater 1 Remove the left and right side panels 2 Remove the grilles 3 Remove the drain pan 4 Loosen the screw that fixes the line flow fan to the fan motor See Photo 7 5 Remove the screw of the center support and remove the support See Photo 10 6 Remove the 2 screws on the left and right sides of the heat exchanger and pull the bear...

Страница 48: ... 1 1 R01 005 103 R01 Z61 102 R01 12G 114 R01 16G 114 R01 12G 115 R01 16G 115 T7W B08 480 T7W B02 480 T7W B09 480 T7W B03 480 18 24 30 36 Including Restrictor valve Capillary tube Including Restrictor valve Capillary tube Including Restrictor valve Capillary tube Including Restrictor valve Capillary tube w Restrictor valve and capillary tube have been added to Specifications of heat exchanger PKH18...

Страница 49: ...1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 3 2 1 1 1 2 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 3 2 1 1 1 2 1 1 1 1 1 1 1 1 2 1 2 2 1 1 1 1 1 1 1 1 1 3 2 FL 1 1 1 2 1 1 1 1 1 1 1 1 2 1 2 2 1 1 1 1 1 1 1 1 1 3 2 MV RT1 RT2 TB2 TB4 C I B F1 2 I B P B 88H 88H MF MF W R FS1 2 FS1 2 26H H H ROOM TEMPERATURE PIPE TEMPERATURE INDOOR COIL 3P L1 L2 GR 3P 1 2 3 2 5µF 440V 250V 6A LY1F DC12V LY2F DC12V PN4N45 K PN4N70...

Страница 50: ...E PANEL INTAKE GRILLE BACK PLATE BACK PLATE TOP PLATE TOP PLATE INTAKE GRILLE DRAIN SOCKET 1 1 1 4 1 1 1 2 1 1 1 1 1 1 4 1 1 1 2 1 1 1 1 1 1 5 1 1 1 2 1 1 1 1 1 1 1 5 1 1 1 2 1 1 1 1 18 24 30 36 FL FL FL R01 12G 662 R01 E01 812 R01 E00 812 R01 E00 811 R01 E01 811 R01 A17 500 R01 50J 317 R01 24K 658 T7W E00 661 R01 12G 691 R01 12G 808 R01 16G 808 R01 E01 641 R01 E00 641 R01 16G 692 R01 12G 523 STRU...

Страница 51: ......

Страница 52: ...2001 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Nov 2003 No OC276 REVISED EDITON A PDF 9 Distributed in Dec 2001 No OC276 New publication effective Nov 2003 Specifications subject to change without notice ...

Страница 53: ...3400 Lawrenceville Suwanee Road Suwanee Georgia 30024 Toll Free 800 433 4822 Toll Free Fax 800 889 9904 www mrslim com Specifications are subject to change without notice ...

Отзывы: