7-2. FUNCTION OF DIP SWITCH
PKFY-P32VGM , PKFY-P40VGM , PKFY-P50VGM
1
2
3
4
5
6
7
8
9
10
1~6
1
2
3
4
5
6
7
8
9
10
1~4
Thermistor<Intake temperature
detection>position
ON
OFF
Filter clogging detection
Provided
Not provided
Filter life
2500hr
100hr
Air intake
Effective
Not effective
Remote indication switching Thermostat ON signal indication Fan output indication
Humidifier control
Always operated while the heating mode
w
1 Operated depends on the condition
w
2
Air flow set in case of
Fix to LOW
w
3
Fix to EXTRA LOW
w
3
Heat thermostat OFF
Depends on setting Remote controller
w
3 Depends
on
SW1-7
Auto restart
Effective
Not effective
Power ON/OFF
Effective
Not effective
Heat pump/Cooling only
Cooling only models
Heat pump models
Louver Available
Not
available
Vane Available
Not
available
Vane swing function
Available
Not available
Vane horizontal angle
Second setting
First setting
Vane cooling limit angle setting
w
4 Horizontal angle
Down A,B,C
Effective
Not
effective
Heater 4 deg up
Not effective
Effective
Target Superheat setting
w
5 9
degrees
6
degrees
Target Subcool setting
15 degrees
10 degrees
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4 5 6 7 8 9 10
ON
OFF
1 2 3 4 5 6
MODELS
SW2
MODELS
SW2 MODELS SW2
PKFY-
P32VGM
PKFY-
P40VGM
Address board
<Initial setting>
Indoor controller board
Indoor controller board
Indoor controller board
<Initial setting>
SW4
Unit
Selection
SW3
Function
Selection
SW2
Capacity
code
setting
SW1
Mode
Selection
Switch Pole
Function
Operation by switch
Remarks
Bult-in remote controller
Indoor unit
Indoor linear expansion
valve opening
NOTE:
w
1 At Heating mode, fan
operating.
w
2 At Heating mode, operat-
ing heat thermostat ON.
w
3 SW1-7=OFF, SW1-8=ON
→
Setting air flow.
SW1-7=ON,
SW1-8=ON
→
Indoor fan stop.
Set while the unit is off.
<Initial setting>
Set for each capacity.
Set while the unit is off.
NOTE:
w
4 At cooling mode, each
angle can be used only 1
hour.
w
5 SW3-9 setting
PKFY-P32VGM
=
OFF
PKFY-P40VGM
=
ON
PKFY-P50VGM
=
OFF
Set while the unit is off.
PKFY-
P50VGM
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6 7 8 9 10
<Initial setting>
ON
OFF
1 2 3 4
The black square ( ) indicates a switch position.
OC179B