Yes
Yes
Yes
Yes
Yes
Fail
Fail
Fail
Fail
OK
NO
NO
NO
NO
OK
OK
OK
26
OCH758
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Check method of DC fan motor (fan motor/indoor controller circuit board)
1
Notes
· High voltage is applied to the connector (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit board and fan motor.)
2
Self check
Symptom : The indoor fan cannot rotate.
Symptom: The fan motor does not stop when pressing the stop button on the remote controller.
The fan motor starts to rotate when turning on the breaker.
Process: The connector for emergency operation on the indoor controller board is possibly set to ON.
Check the setting of SWE.
Set SWE to OFF if it is set to ON.
Is there contact failure?
Is the voltage normal?
Does the voltage repeat
0 V DC and 15 V DC?
Indoor controller board fuse check
Wiring contact check
Contact of fan motor connector (CNMF)
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board.
TEST POINT
1
:
V
DC
(between 1 (+) and 4 (−) of the fan connector): V
DC
310–340 V DC
TEST POINT
2
:
V
CC
(between 5 (+) and 4 (−) of the fan connector): V
CC
15 V DC
Sensor signal check
Measure the voltage between CNMF
6
and
3
0 V DC
and 15 V DC in the indoor controller circuit board.
Correct the wiring.
Is the fuse normal?
Check the operation.
Replace the indoor
controller board.
Replace the fuse.
Check the operation.
Check the operation of fan.
Check the operation.
Complete.
Complete.
Complete.
Complete.
Replace the defective fan motor.
Replace the indoor
controller board.
Replace the indoor
controller board.
Replace the defective fan motor.
Replace the defective fan motor.