background image

11

PKA-A30FA PKA-A30FAL  PKA-A36FA  PKA-A36FAL

SW1

Table 1

Service board

SW2

Table 2

Service board

Service board

Service board

1  2  3  4  5

ON

OFF

1  2  3  4  5

ON

OFF

MODELS

PKA-

A24FA(L)

MODELS

PKA-

A30FA(L)

MODELS

PKA-

A36FA(L)

1  2  3  4  5

ON

OFF

1  2  3  4  5

ON

OFF

Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual.

For A24/30/36FAL

For A24/30/36FA

INTAKE

CN20

(RED)

LIQUID

CN21

(WHT)

PIPE

CN29

(BLK)

TH5

TH1

TH2

REMOCON

CN22

(BLU)

TB5

R.B

TRANSMISSION WIRES DC12V

SWE

ON
OFF

SW2 SW1

LED3 LED2 LED1

ZNR

FUSE

CN24

(YLW)

MV

6

W.B

BZ

CNB

RECEIVER

RU

LED1 LED2 SW2 SW1

9

9

FAN

(WHT)

1

1

1

1

1

1

1

1

1

2

3

2

1

2

1

2

1

2

3

3

2

3

3

2

3 5

BLK

WHT

WHT

RED

RED

C

X4

BCR

TO

OUTDOOR

UNIT

TB4

YLW
ORN

YLW
ORN

BRN

YLW

ORN

BLK

WHT

BRN

ORN

P.B

I.B

POWER

CNDK

(RED)

CNSK

(RED)

DC13.1V

CN2S

(WHT)

POWER

CND

(ORN)

POWER

CN2D

(WHT)

A-CONTROL

CN3C

(BLU)

Refer to tables 1 and 2 
for service PCB.

+

1

1

2

1

2

CN30

(BLK)

1

3

MF

M

1~

M

U

2

1

TB6

2

1

S2
S3

S1

CN32(

WHT)

CN2L(

RED)

1

3

1

4

CN51(

WHT)

CN41(

WHT)

5

1

9

1

6

1

VANE

CN6V

(GRN)

WIRELESS

CN90

(WHT)

P.B

INDOOR POWER BOARD

[LEGEND]

NAME

I.B

INDOOR CONTROLLER BOARD

FUSE

FUSE (6.3A/250V)

ZNR

VARISTOR

CN2L

CONNECTOR <LOSSNAY>

CN32

CONNECTOR <REMOTE SWITCH>

CN41

CONNECTOR <HA TERMINAL-A>

CN24

CONNECTOR <BACK-UP HEATING>

CN30

CONNECTOR <LLC>

CN51

CONNECTOR <CENTRALLY CONTROL>

SW1

SWITCH <MODEL SELECTION>

+

See Table 1.

SW2

SWITCH <CAPACITY CODE>

+

See Table 2.

SWE

SWITCH <EMERGENCY OPERATION>

X4

RELAY <FAN MOTOR>

BCR

POWER SUPPLY <R.B>

LED1

POWER SUPPLY <I.B>

LED2

TRANSMISSION <INDOOR-OUTDOOR>

LED3

FAN CONTROL ELEMENT

C

CAPACITOR <FAN MOTOR> 

FAN MOTOR
VANE MOTOR

MF

MV

SYMBOL

NAME

TB4

TERMINAL BLOCK <INDOOR/OUTDOOR

CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER

TRANSMISSION LINE >
ROOM TEMP.THERMISTOR

<32

˚

F/15k

Ω

, 77

˚

F/5.2k

Ω

 DETECT>

PIPE TEMP.THERMISTOR/LIQUID

<32

˚

F/15k

Ω

, 77

˚

F/5.2k

Ω

 DETECT>

COND./EVA.TEMP.THERMISTOR

<32

˚

F/15k

Ω

, 77

˚

F/5.2k

Ω

 DETECT>

TB5,TB6

TH5

TH1

TH2

W.B

WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT 
BUZZER
LED <RUN INDICATOR >
LED <HOT ADJUST>
SWITCH <HEATING ON/OFF>
SWITCH <COOLING ON/OFF>

WIRED REMOTE CONTROLLER BOARD

R.B

RU

BZ
LED1
LED2
SW1
SW2

NAME

SYMBOL

Notes:
1.  SymboIs used in wiring diagram above are,                : Connector,                : Terminal block.
2.  Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3.  Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of 
    power and signal.

+

1. Use copper supply wires.

[Self-diagnosis]
Please refer to technical manuals etc.

Содержание Mr.SLIM PKA-A18GA

Страница 1: ...RS 16 8 AIR FLOW DATA 18 9 NOISE CRITERION CURVES 24 10 OPTIONAL PARTS 27 Indoor unit Model names PLA A BA PKA A GA PKA A GAL PKA A FA PKA A FAL Outdoor unit Model name No OCS12 REVISED EDITION A SPLIT TYPE HEAT PUMP AIR CONDITIONERS PUZ HA30NHA PUZ HA36NHA November 2008 HYPER HEATING INVERTER Revision PUZ HA30NHA is added in REVISED EDITION A Some descriptions have been modified Please void OCS12...

Страница 2: ...me Service Ref PUZ HA30 36NHA PUZ HA30 36NHA Model name Service Ref Service Manual No PLA A18 30 36BA PLA A18BA PLA A18BA1 OCH420 OCB420 PKA A18GA PKA A18GA GA1 GA2 OC369 PKA A18GAL PKA A18GAL GAL1 GAL2 PKA A30 36FA PKA A36FA FA1 FA2 PKA A30 36FAL PKA A36FAL FAL1 FAL2 PLA A30BA1 PKA A30FA2 PKA A30FAL2 PLA A36BA PLA A36BA1 1 REFERENCE SERVICE MANUAL ...

Страница 3: ...33 1 16 37 3 8 235 9 1 4 H mm inch 298 35 11 3 4 1 3 8 340 13 3 8 Weight Unit Grille kg 25 6 258 35 10 3 16 1 3 8 23 6 28 Weight Unit Grille lbs 55 13 62 24 53 Field drain pipe size mm inch O D 32 1 1 4 I D 20 13 16 Remote Controller Attached in Grille Attached in Indoor unit Outdoor unit MCA A 28 MOCP A 40 Fan Motor F L A 0 4 0 4 Fan Motor Output W 60 60 Compressor Type ANB33FJCMT ANB33FJEMT ANB3...

Страница 4: ...ain pipe connected to VP 25 Suspension bolt M10 or W3 8 Branch duct hole Fresh air intake hole Branch duct hole Ceiling hole Suspension bolt pitch Suspension bolt pitch Ceiling hole 5 16 5 16 23 13 16 24 13 32 DEFROST STAND BY lamp Receiver Operation lamp For wiring replacement kit terminal block 6 5 16 6 5 16 1 2 3 15 16 5 1 8 13 25 32 3 17 32 3 15 16 3 15 16 3 17 32 6 9 16 6 3 32 5 29 32 6 7 8 1...

Страница 5: ... 245 1 31 32 50 15 9 16 395 15 3 4 400 7 15 32 190 2 3 8 60 2 3 4 70 1 3 8 35 3 1 8 79 6 5 16 160 1 9 16 40 27 3 4 705 Air outlet 9 1 4 235 Less than 19 32 15 7 25 32 198 2 3 4 70 9 21 32 245 2 3 8 60 9 1 4 235 2 3 32 53 13 3 8 340 28 5 32 715 Air intake 8 27 32 225 13 3 8 340 3 5 32 80 11 1 32 280 9 3 16 233 39 990 Wiring entrance holes Service space required around indoor unit Front view top ope...

Страница 6: ...2 2 9 32 58 Field drain pipe size 13 16 20mm I D 1 25 32 45 1 25 32 45 1 25 32 45 A B C 1 3 16 30 1 3 16 30 1 17 32 39 B A 2 29 32 74 C 3 27 32 98 1 15 32 37 2 29 32 74 1 15 32 37 2 9 16 65 5 32 4 1 17 32 39 1 9 16 39 3 15 16 100 1 1 4 32 1 15 32 37 3 15 16 100 5 32 4 21 23 32 552 Air outlet 44 3 32 1120 13 3 8 340 7 3 4 197 1 2 13 2 15 32 62 5 9 1 4 235 9 1 4 235 55 1 8 1400 9 7 16 240 42 29 32 1...

Страница 7: ...0 Air intake 9 1 4 235 7 7 32 183 2 5 32 55 4 23 32 120 27 5 16 694 Air outlet 9 1 4 235 66 1 8 1680 4 3 8 111 4 1 32 102 43 11 16 1110 Drain hose 31 32 25 7 3 4 197 9 1 4 235 1 25 32 45 Gas pipe Liquid pipe MODEL 36 3 8 5 8 Sleeve 1 ø3 17 32 ø3 15 16 ø90 ø100 Through hole ø3 17 32 ø90 1 Sleeves are available on the market Field drain pipe size 13 16 20mm I D Front view Knockout hole for left pipi...

Страница 8: ...e Knockout Conduit hole 2 27 1 1 16 Knockout 9 2 3 5 8 92 3 5 8 65 2 9 16 45 1 25 32 40 1 9 16 27 1 1 16 55 2 3 16 23 29 32 73 2 7 8 63 2 1 2 Front piping hole Knockout Front trunking hole Knockout Conduit hole 2 27 1 1 16 Knockout 9 2 3 5 8 371 14 19 32 330 13 30 1 3 16 175 6 7 8 600 23 5 8 175 6 7 8 42 1 21 32 66 2 5 8 950 37 13 32 322 12 11 16 1350 53 5 32 635 25 19 3 4 417 16 13 32 370 14 9 16...

Страница 9: ...ated in the past appear on the display W B RU BZ LED1 LED2 SW1 SW2 OPTION PART PCB FOR WIRELESS REMOTE CONTROLLER RECEIVING UNIT BUZZER LED OPERATION INDICATION GREEN LED PREPARATION FOR HEATING ORANGE EMERGENCY OPERATION HEAT DOWN EMERGENCY OPERATION COOL UP Be sure to turn off the power source and then disconnect fan motor connector Failure to do so will cause trouble in fan motor CN24 CONNECTOR...

Страница 10: ...R BACK UP HEATING CN30 CONNECTOR LLC CN51 CONNECTOR CENTRALLY CONTROL SW1 SWITCH MODEL SELECTION See Table 1 SW2 SWITCH CAPACITY CODE See Table 2 SWE SWITCH EMERGENCY OPERATION X4 RELAY FAN MOTOR BCR POWER SUPPLY R B LED1 POWER SUPPLY I B LED2 TRANSMISSION INDOOR OUTDOOR LED3 FAN CONTROL ELEMENT C CAPACITOR FAN MOTOR FAN MOTOR VANE MOTOR MF MV SYMBOL NAME TB4 TERMINAL BLOCK INDOOR OUTDOOR CONNECTI...

Страница 11: ...41 CONNECTOR HA TERMINAL A CN24 CONNECTOR BACK UP HEATING CN30 CONNECTOR LLC CN51 CONNECTOR CENTRALLY CONTROL SW1 SWITCH MODEL SELECTION See Table 1 SW2 SWITCH CAPACITY CODE See Table 2 SWE SWITCH EMERGENCY OPERATION X4 RELAY FAN MOTOR BCR POWER SUPPLY R B LED1 POWER SUPPLY I B LED2 TRANSMISSION INDOOR OUTDOOR LED3 FAN CONTROL ELEMENT C CAPACITOR FAN MOTOR FAN MOTOR VANE MOTOR MF MV SYMBOL NAME TB...

Страница 12: ...ct Input Fuse T6 3AL250V X51 X52 X55 Relay SS Connector Connection for Option SYMBOL M NET ADAPTER NAME TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 Terminal Block M net connection Connector Transmission Connector Power Supply Connector M NET communication Switch Status of communication Switch Address setting 1s digit Switch Address setting 10ths digit LED Power Supply DC5V LED Connecti...

Страница 13: ...onnection 15 88 5 8 Refrigerant LIQUID pipe connection 9 52 3 8 Stop valve with service port Strainer 100 Power receiver Electronic expansion valve B Electronic expansion valve C Electronic expansion valve A Strainer 100 Replace filter Strainer 100 Strainer 100 Thermistor TH6 Outdoor 2 phase pipe Thermistor TH3 Outdoor pipe Charge plug Low pressure Charge plug High pressure Heat inter change circu...

Страница 14: ...ixed FOR THE COMBINATION OF OUTDOOR UNIT PUZ HA NHA 1 4 1 2 1 0 0 8 72 F 22 C 72 F 22 C 68 F 20 C 68 F 20 C 64 F 18 C 64 F 18 C 61 F 16 C 61 F 16 C 90 32 C 70 21 C 50 10 C 30 1 C 23 5 C 110 43 C 1 2 1 0 0 8 0 6 0 4 INDOOR W B CAPACITY RATIO TOTAL INPUT RATIO INDOOR W B OUTDOOR D B F Cooling performance curve ...

Страница 15: ...NPUT RATIO CAPACITY RATIO 0 60 0 80 1 00 1 20 1 40 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 60 26 23 21 18 15 12 9 7 4 1 2 4 7 10 13 16 Outdoor ambient temp 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 60 26 23 21 18 15 12 9 7 4 1 2 4 7 10 13 16 FWB CWB FWB CWB Heating input Indoor intake air dry bulb temperature F DB Indoor intake air dry bulb temperature F DB ...

Страница 16: ...NG CAPACITY CORRECTION FACTORS 7 3 CAPACITY CORRECTION Cooling and heating capacity is lowered according to pipe length Capacity can be obtained by referring to the capacity curves below Corrected pipe length m actual pipe length m number of bends x 0 3 m Corrected pipe length ft actual pipe length ft number of bends x 1 ft Cooling Heating 100 95 90 85 80 75 70 5 16 10 33 15 50 20 70 25 80 30 100 ...

Страница 17: ...ter charging the unit with refrigerant note the added refrigerant amount on the service label attached to the unit Be careful when installing multiple units Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance Model Max height difference Additional refrigerant charging amount Max pipe length 30 m 33 m 37 m 40 m 43 m 46 m 49 ...

Страница 18: ...irflow Air speed Coverage range CFM ft sec m sec ft m Airflow Air speed Coverage range PKA A36FAL PKA A36FA 990 17 7 5 4 50 15 3 PKA A30FAL PKA A30FA 705 16 1 4 9 41 12 4 The air coverage range is the distance to which the 0 8 ft sec air can reach when air is blown out horizontally from the unit at the High notch position The coverage range should be used only as a general guideline since it varie...

Страница 19: ...se condensation and dripping may occur Branch duct hole 14 1 8 2 8 burring hole Indoor unit 5 29 32 150 cut out hole Fresh air intake hole 6 7 8 175 burring hole pitch Drain pipe Fresh air intake hole diagram Unit inch mm Refrigerant pipe 3 1 8 2 8 burring hole Branch duct hole diagram view from either side 4 29 32 125 burring hole pitch 3 15 16 100 cut out hole Ceiling 6 7 32 158 120 120 13 25 32...

Страница 20: ...G 10 2 2 PLA A36BA Multifunction casement Standard filter Multifunction casement High efficiency filter Taking air into the unit Taking air into the unit 3 Fresh air intake amount static pressure characteristics 1 PLA A18BA PLA A30BA Multifunction casement High efficiency filter Multifunction casement Standard filter Q 0 B A C 1 Curve in the graphs Duct characteristics at site Q A E C 2 Q Qa A D 3...

Страница 21: ...onnector 5 Branch duct and change of outlet numbers 4 way air flow and branch duct Branch duct should be connected to one of the branch duct holes on the main unit Branch duct Air intake Air outlet 3 way air flow and branch duct Close the outlet on the side of branch duct and air flows in 3 directions Branch duct Air intake Air outlet Air outlet closed position Air outlet closed position 2 way air...

Страница 22: ...flow rate Airflow rate Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 0 0 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 0 2 4 6 8 10 CMM 0 2 4 6 8 10 12 CMM High Low 0 10 4 20 8 30 12 0 0 50 100 150 200 250 CFM 2 4 6 8 CMM 0 50 100 150 200 250 30...

Страница 23: ... 8 CMM Airflow rate Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 Static pressure Pa in W G 10 2 0 0 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 90 36 100 40 10 4 20 8 30 12 40 16 50 20 60 24 70 28 80 32 90 36 100 40 0 2 4 6 8 10 CMM 0 2 4 6 8 10 12 CMM 0 10 4 20 8 30 12 0 0 50 100 150 200...

Страница 24: ...34 Low 32 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar UNIT 5ft MICROPHONE CEILING 9 1 INDOOR UNIT PLA A30BA NOTCH SPL dB LINE High 34 Medium1 32 Medium2 30 Low 28 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 200...

Страница 25: ...50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 bar BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE High NOTCH Low 49 SPL dB 46 LINE PKA A36FA PKA A36FAL 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 ...

Страница 26: ...TE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 PUHZ HA30NHA PUHZ HA36NHA COOLING MODE HEATING 52 SPL dB 53 LINE 5 ft 3 3 ft MICROPHONE UNIT GROUND 9 2 OUTDOOR UNIT ...

Страница 27: ...or for CN30 LLC PAC SE57RA E Connector for CN24 Back up heating PAC SE56RA E PKA A30 36FA L L shape connection pipe PAC SC84PI E Multi function casement High efficiency filter element Flange for fresh air intake PAC SH53TM E is needed Decoration panel with Wired remote controller i see sensor corner panel Wireless signal receiver Space panel Air outlet shutter plate Decoration panel PAC SH53TM E P...

Страница 28: ...30 36 needs 2 pieces PAC SH63AG E Drain pan PAC SG64DP E Distribution pipe for twin use MSDD 50SR E HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Nov 2008 No OCS12 REVISED EDITION A PDF 6 Distributed in Oct 2007 No OCS12 PDF 7 Made in Japan New publication effective Nov 2008 Specifications subject to ch...

Отзывы: