 Warning:

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-
ing particles, oils, moisture, or any other contaminant.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

7.2. Drain piping work

Ensure that the drain piping is downward (pitch of more than 1/100) to the
outdoor (discharge) side. Do not provide any trap or irregularity on the way.

Ensure that any cross-wise drain piping is less than 20 m (excluding the differ-
ence of elevation). If the drain piping is long, provide metal braces to prevent it
from waving. Never provide any air vent pipe. Otherwise drain may be ejected.

Use a hard vinyl chloride pipe O.D. ø32 for drain piping.

Ensure that collected pipes are 10 cm lower than the unit body’s drain port.

Do not provide any odor trap at the drain discharge port.

Put the end of the drain piping in a position where no odor is generated.

Do not put the end of the drain piping in any drain where ionic gases are generated.

[Fig. 7.2.1] (P.3)

A

Downward slope 1/100 or more

B

Drain hose (Accessory)

C

Indoor unit

D

Collective piping

E

Maximize this length to approx. 10 cm

1.

Insert the drain hose (accessory) into the drain port.
(The drain hose must not be bent more than 45

°

  to prevent the hose from

breaking or clogging.)
The connecting part between the indoor unit and the drain hose may be dis-
connected at the maintenance. Fix the part with the accessory band, not be
adhered.

2.

Attach the drain pipe (O.D. ø32 PVC TUBE, field supply).
(Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the
band (small, accessory).)

3.

Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the
socket (including elbow).

[Fig. 7.2.2] (P.3)

A

Indoor unit

B

Insulation pipe (short) (accessory)

C

Tie band (accessory)

D

Band fixing part

E

Insertion margin

F

Drain hose (accessory)

G

Drain pipe (O.D. ø32 PVC TUBE, field supply)

H

Insulating material (field supply)

I

Max.145 

±

 5 mm

7. Connecting refrigerant pipes and drain pipes

7.1. Refrigerant piping work

This piping work must be done in accordance with the installation manuals for both
outdoor unit.

For constraints on pipe length and allowable difference of elevation, refer to
the outdoor unit manual.

The method of pipe connection is brazing connection.

 Caution:

Install the refrigerant piping for the indoor unit in accordance with the
following.

1.

Cut the tip of the indoor unit piping, remove the gas, and then remove the
brazed cap.

[Fig. 7.1.1] (P.3)

A

Cut here

B

Remove brazed cap

2. Pull out the thermal insulation on the site refrigerant piping, braze the unit

piping, and replace the insulation in its original position.
Wrap the piping with insulating tape.

Note:

When blazing the refrigerant pipes, be sure to blaze, after covering a wet
cloth to the pipes of the units in order to prevent it from burning and
shrinking by heat.

[Fig. 7.1.2] (P.3)

A

Cool by a wet cloth

Pay strict attention when wrapping the copper piping since wrapping the
piping may cause condensation instead of preventing it.

[Fig. 7.1.3] (P.3)

A

Thermal insulation tubing (small)

B

Caution:

Pull out the thermal insulation on the refrigerant piping at the site, braze the pip-
ing, and replace the insulation in its original position.

Take care to ensure that condensation does not form on exposed copper piping.

C

Refrigerant piping (liquid)

D

Refrigerant piping (gas)

E

Main body

F

Thermal insulation tubing (large)

G

Site refrigerant piping

H

Ensure that there are no gaps between the insulation and the main body.

I

Thermal insulation tubing (small) (supplied) 1

J

Ties (large) (supplied) 4

K

Ensure that there is no gap here. Place join upwards.

L

Thermal insulation tubing (medium) (supplied) 2

M

Thermal insulation

N

Pull

O

Flared pipe end

P

Wrap with damp cloth

Q

Return to original position

R

Ensure that there is no gap here.

Cautions On Refrigerant Piping

s

s

s

s

s

Be sure to use non-oxidative brazing for brazing to ensure that no for-
eign matter or moisture enter into the pipe.

s

s

s

s

s

Be sure to apply refrigerating machine oil over the flare connection seat-
ing surface and tighten the connection using a double spanner.

s

s

s

s

s

Provide a metal brace to support the refrigerant pipe so that no load is
imparted to the indoor unit end pipe. This metal brace should be pro-
vided 50 cm away from the indoor unit’s flare connection.

6.1. Refrigerant pipe and drain pipe specifications

Refrigerant pipe

(Brazing connection)

Model

Item

250

Liquid pipe

ø 9.52

Gas pipe

ø 22.2

Drain pipe

O.D. ø 32

6.2. Refrigerant pipe, drain pipe

[Fig. 6.2.1] (P.2)

A

Air inlet

B

Refrigerant piping (liquid)

C

Refrigerant piping (gas)

D

Control box

E

Drain pipe

F

Air outlet

WT05750X01_GB.p65

09/10/19, 16:30

9

Содержание Mr.Slim PEA-RP250WHA

Страница 1: ...Air Conditioners INDOOR UNIT PEA RP250 WHA GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Страница 2: ...D Washers accessory E M10 hanging bolt field supply 5 5 3 Fig 5 1 1 Fig 5 1 2 Fig 5 3 1 5 1 6 6 2 Fig 6 2 1 A Indoor unit s bottom surface 701 494 235 1034 1324 A A B A C D C E D A Air inlet B Refrigerant piping liquid C Refrigerant piping gas D Control box E Drain pipe F Air outlet 165 52 100 244 30 424 A B E C D F Fig 4 1 1 Fig 3 2 1 A Access door B Electrical parts box C Air inlet D Air outlet ...

Страница 3: ...en the insulation and the main body I Thermal insulation tubing small supplied 1 J Ties large supplied 4 K Ensure that there is no gap here Place join upwards L Thermal insulation tubing medium supplied 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here M M Q R P O N Fig 7 2 2 A Indoor unit B Insulation pipe short...

Страница 4: ...g 8 0 1 B G E F H A I C C D D A Air inlet B Air filter supplied at site C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct work length 850 mm or more Fig 9 2 2 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L N C A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller ...

Страница 5: ...th the transmis sion terminal 9 3 Fig 9 5 1 Fig 9 3 4 9 5 A Terminal bed box B Knockout hole C Remove Fig 9 3 1 Fig 9 3 2 B C A A B I J F G E L N 1 2 L S M2 M1 K H O N M L N M2 M1 M2 S M1 A B C D A Screw holding cover 2pcs B Cover SWA SW5 SW14 SW12 SW11 SWC Indoor controller board Fig 9 3 3 E Use PG bushing to keep the weight of the cable and external force from being applied to the power supply t...

Страница 6: ...frigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being ...

Страница 7: ...fied capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air conditioner units Washing them may cause an electric shock Be careful that the installation base is not damaged by long use If the damage is left uncorrected the unit may fall and cause personal injury or property damage Install the drain piping ac...

Страница 8: ...pipes Insulate all indoor pipes with form polyethylene insulation with a minimum density of 0 03 and a thickness as specified in the table below 1 Select the thickness of insulating material by pipe size Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high...

Страница 9: ...E Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supply H Insulating material field supply I Max 145 5 mm 7 Connecting refrigerant pipes and drain pipes 7 1 Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit For constraints on pipe length and allowable difference of elevation refer to the outdoor unit...

Страница 10: ...rd not to touch the fan Fig 8 0 1 P 4 A Air inlet B Air filter supplied at site C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct work length 850 mm or more Table 1 Transmission cable length Less than 80 m Facility example for noise judgment Types of transmission cables Residence or independent store without noise VCTF VCTFK C...

Страница 11: ...oller Shield wire connection Fig 9 3 4 P 5 A Terminal bed B Round terminal C Shield wire D Insulation tape To keep the earth wire of the shielded cable from coming in con tact with the transmission terminal 5 After wiring is complete make sure again that there is no slack on the connec tions and attach the cover onto the terminal bed box in the reverse order of removal Notes Do not pinch the cable...

Страница 12: ...Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Отзывы: