9.  Test run

•  If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit)

PLEASE WAIT

For about 2 minutes 
following power-on

After LED 1, 2 are lighted, LED 2 is turned 

off, then only LED 1 is lighted. (Correct 

operation)

• For about 2 minutes after power-on, operation of the 

remote controller is not possible due to system start-up. 

(Correct  operation)

PLEASE WAIT →

 Error code

After about 2 
minutes has expired 
following power-on

Only LED 1 is lighted. 

 LED 1, 2 blink.

• Connector for the outdoor unit’s protection device is not  

connected.

• Reverse or open phase wiring for the outdoor unit’s power 

terminal block (L1, L2, L3)

Display messages do not appear 
even when operation switch is 

turned ON (operation lamp does 

not light up).

Only LED 1 is lighted. 

 LED 1, 2 blinks 

twice, LED 2 blinks once.

• Incorrect wiring between indoor and outdoor units (incorrect 

polarity of S1, S2, S3)

• Remote controller wire short

[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller

Symptom

Remark

Beeper sounds/OPERATION INDICATOR 

lamp flashes (Number of times)

1

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

For details, check the LED 

display of the outdoor controller 

board.

2

Compressor overcurrent interruption

3

Open/short of outdoor unit thermistors

4

Compressor overcurrent interruption (When compressor locked)

5

Abnormal high discharging temperature/49C worked/ insufficient refrigerant

6

Abnormal high pressure (63H worked)/ Overheating safeguard operation

7

Abnormal temperature of heat sink

8

Outdoor unit fan protection stop

9

Compressor overcurrent interruption/Abnormal of power module

10

Abnormality of super heat due to low discharge temperature

11

Abnormality such as overvoltage or voltage shortage and abnormal 

synchronous signal to main circuit/Current sensor error

12

13

14

Other errors (Refer to the technical manual for the outdoor unit.)

*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does 

not come on, there are no error records.

*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was 

received, the specified refrigerant address is incorrect.

•  On wireless remote controller

  The continuous buzzer sounds from receiving section of indoor unit.

  Blink of operation lamp

•  On wired remote controller

  Check code displayed on the LCD.

•  Check that all LEDs on the two control boards on the indoor unit are lit or blinking (3 each, 6 total). 

9.3.  Test run

9.3.1.  Using wireless remote controller (option)

[Fig. 9-3] (P.11)

① 

Turn on the power to the unit at least 12 hours before the test run.

  Press the TEST RUN button 

 twice continuously.

  (Start this operation from the status of remote controller display turned off.)

 

TEST RUN

 and current operation mode are displayed.

  Press the MODE button 

 to activate COOL mode, then check whether cool 

air is blown out from the unit.

  Press the MODE button 

 to activate HEAT mode, then check whether warm 

air is blown out from the unit.

  Press the FAN button 

 and check whether fan speed changes.

  Press the VANE button 

 and check whether the auto vane operates properly.

  Press the ON/OFF button to stop the test run.

Note: 

•  Point the remote controller towards the indoor unit receiver while 

following steps 

 to 

.

•  It is not possible to run the in FAN, DRY or AUTO mode.

[Output pattern A] Errors detected by indoor unit

Wireless remote controller

Wired remote 

controller

Symptom

Remark

Beeper sounds/OPERATION 

INDICATOR lamp flashes 

(Number of times)

Check code

1

P1

Intake sensor error

2

P2, P9

Pipe (Liquid or 2-phase pipe) sensor error

3

E6, E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error

5

P5

Drain pump error

6

P6

Freezing/Overheating safeguard operation

7

EE

Communication error between indoor and outdoor units

8

P8

Pipe temperature error

9

E4

Remote controller signal receiving error

10

11

PB

Fan motor error

12

Fb

Indoor unit control system error (memory error, etc.)

No sound

– –

No corresponding

Содержание Mr.Slim PEA-RP100

Страница 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP100 125 140GAA ORIGINAL English FOR INSTALLER ...

Страница 2: ...t without inlet duct When hanging the indoor unit directly without inlet duct When connecting inlet duct When installing the suspension fixtures prior to installation of the indoor unit without inlet duct When hanging the indoor unit directly without inlet duct Electric box Access door 2 Access door 1 Ceiling Access door 2 Ceiling beam Supply air Intake air Electric box Min 300mm Min 500mm Min 500...

Страница 3: ...ter of gravity 5 1 98 680 200 1300 235 Ⓐ Ⓐ Ⓑ 4 1 A 30 B Ⓐ Ⓑ Ⓐ 1 A 30 B 10 Ⓐ Fig 5 1 2 Fig 5 1 3 Ⓐ Nut Ⓑ Washer Ⓐ Be sure to attach a U shaped washer 4 washers in total 6 øB øA ⓐ ⓑ Fig 6 1 ⓐ Indoor unit ⓑ Outdoor unit 6 1 Model A B PEA RP100 125 140 ø15 88 ø9 52 ...

Страница 4: ...ping Ⓓ Gas end of refrigerant piping Ⓔ Site refrigerant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓐ Ⓑ Ⓒ Ⓓ Ⓕ Ⓖ Ⓔ Ⓗ Ⓗ Ⓚ Ⓛ Ⓙ Ⓘ Ⓙ Ⓞ Ⓞ Ⓝ Ⓝ 20 20 20 20 Fig 6 2 1 Fig 6 2 4 Fig 6 2 2 Fig 6 2 3 ⓐ Flare nut ⓑ Copper tube ⓐ Burr ⓑ Copper tube pipe ⓒ Spare reamer ⓓ Pipe cutter Fig 6 2 5 Fig 6 3 1 ⓐ Flaring tool ⓑ Die ⓒ C...

Страница 5: ...Air outlet Ⓒ Access door Ⓓ Ceiling surface Ⓔ Canvas duct Ⓕ Keep duct work length 850 or more Ⓖ Connect common reference potential wire between duct work to air conditioner Ⓐ Inlet duct flange Ⓑ Return air temperature sensor Ⓒ Sensor protection plate Ⓓ Sensor fixture Ⓔ Inlet duct Ⓔ S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 1 1 2 2 S3 S1 S2 L TB4 TB TB15 CND CND CN3C CN3C CN22 N S3 Ⓐ Ⓑ Ⓒ Ⓕ Ⓖ Ⓓ Indoor Control...

Страница 6: ...2 1 Fig 8 2 2 8 Ⓐ Ⓑ Ⓒ Ⓓ Ⓔ Ⓙ Ⓗ Ⓕ Ⓖ Ⓘ 1 2 M1 M2 S Ⓛ Ⓚ Fig 8 2 5 Ⓐ Indoor terminal block Ⓑ Earth wire green yellow Ⓒ Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord 2 0 mm2 or more Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Ⓐ Always install an earth wire 1 core 1 5 mm2 ...

Страница 7: ...ller cord through the cut out upper case then seal the cut out notch with putty similarly as above Ⓒ Wall Ⓓ Conduit Ⓔ Lock nut Ⓕ Bushing Ⓖ Switch box Ⓗ Remote controller cord Ⓘ Seal with putty Ⓙ Wood screw Ⓕ Ⓐ Ⓗ Ⓒ Ⓓ Ⓔ Ⓖ Ⓘ Ⓘ Ⓘ Ⓗ Ⓑ Ⓙ Ⓗ B 1 B 2 Fig 8 3 2 8 Ⓐ AB TB6 Ⓑ Ⓐ To the terminal block on the indoor unit Ⓑ TB6 No polarity Fig 8 3 3 30 46 30 30 120 83 5 Ⓐ Ⓑ Ⓒ Ⓐ Remote controller profile Ⓑ Require...

Страница 8: ... Ⓒ Ⓐ Fix tightly with tape Ⓑ Remote controller wire Ⓒ Order wire Indoor unit Fig 8 4 2 Fig 8 4 5 Ⓗ Ⓙ Ⓘ When using the switch box When installing directly on the wall Ⓐ 150 mm 5 15 16 inch Ⓑ Remote controller wire Ⓒ Wiring pipe Ⓓ Locknut Ⓗ Seal around here with putty Ⓘ Remote controller wire Ⓙ Seal around here with putty Ⓔ Bushing Ⓕ Switch box Ⓖ Seal around here with putty Ⓒ Ⓓ Ⓑ Ⓕ Ⓔ Ⓖ Ⓐ Wall 8 8 4 ...

Страница 9: ...e lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 4 9 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks ...

Страница 10: ...er 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 Ⓐ CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHEC...

Страница 11: ...ACK DAY MONITOR SET CLOCK ON OFF Ⓐ Ⓑ Ⓓ Ⓒ Ⓖ Ⓔ Ⓕ Ⅰ Ⅱ Ⅲ Ⅳ Ⅰ Ⅰ Ⅳ Ⅱ Ⓐ Filter button Enter button Ⓑ TEST button Ⓒ Set Time button Ⓓ Timer On Off button Set Day button Ⓔ Mode selection button Ⓕ Set temperature button Ⓖ Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number Ⅰ Ⅱ Ⅲ Ⅳ CHECK CHECK CHECK CHECK ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOU...

Страница 12: ...pe Ⓓ Gas pipe Ⓔ Stop valve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R410A Ⓛ Gauge manifold valve for R410A Ⓜ Service port 10 1 ...

Страница 13: ...er to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of...

Страница 14: ...n a space of less than 500mm is available below the unit between the unit and the ceiling At least 300 mm of space should be left below the unit as shown in Fig 3 2 4 Fig 3 2 5 Create access door 3 below the electric box and the unit as shown in Fig 3 2 6 Fig 3 2 1 P 2 Fig 3 2 2 P 2 Fig 3 2 3 P 2 Fig 3 2 4 P 2 Fig 3 2 5 P 2 Fig 3 2 6 P 2 3 3 Indoor unit accessories The unit is provided with the fo...

Страница 15: ...rant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓛ Ensure that there is no gap here Ⓜ Plate on main body Ⓝ Band accessory Ⓞ Ensure that there is no gap here Place join upwards 0 0 4 6 1 Refrigerant pipe Fig 6 1 P 3 ⓐ Indoor unit ⓑ Outdoor unit Refer to the Instruction Manual that came with the outdoor unit for t...

Страница 16: ...nting the back flow Charge hose for R410A Service port Stop valve Close Open Stop valve Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 6 5 Drain piping work Fig 6 5 P 4 Ⓐ Insulator Ⓑ Drain pipe R1 Ⓒ Drain pan Ⓓ 70 mm Ⓔ 2 Ⓕ 70 mm Ⓕ 35 mm Ⓖ Downward slope 20 mm m or more Ⓗ Drain trap Ⓘ The drain pipe should extend below this level Ⓙ Open drain In connect...

Страница 17: ...ly If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire Do not pinch the c...

Страница 18: ...ll portion inside the bottom case oblique section by a knife or a nipper Take out the connected remote controller wire to the terminal block through this space 6 Install the lower case on the switch box or directly on the wall Fig 8 4 8 P 9 Mounting the cover Fig 8 4 9 P 9 Caution Insert the cover securely until the clicking sound is made If not doing so the cover may fall 8 4 Remote controller wi...

Страница 19: ...nit number Press the TEMP button Ⓒ and Ⓓ to set the unit number to 07 Direct the wireless remote controller toward the receiver of the indoor unit and press the Minute button Ⓑ Selecting a mode Enter 08 to change the external static pressure setting using the Ⓒ and Ⓓ buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the Hour button Ⓐ Current setting num...

Страница 20: ...d is switched Check operation of the outdoor unit fan Release test run by pressing the ON OFF button Stop Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor uni...

Страница 21: ...ical manual for the outdoor unit 1 If the beeper does not sound again after the initial two beeps to confirm the self check start signal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified ...

Страница 22: ...on But never use naked fire or steam 9 Test run For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED 1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoo...

Страница 23: ......

Страница 24: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KD79M111H02 ...

Отзывы: