Mitsubishi Electric Mr. Slim PCA-RP-GA Скачать руководство пользователя страница 6

6

 

L

1

N

2

S1

S2 S3

5. Drainage piping work

Installing procedures (Fig. 5-2)

1. Attach the joint socket 

5

 supplied with the unit to the drain port on the unit with a

vinyl chloride adhesive.

2. Fasten the socket cover 

6

 supplied with the unit to the joint socket 

5

.

3. Attach the field drain tubing (VP20) to the joint socket 

5

 with a vinyl chloride

adhesive.

4. Wrap the drain tubing cover 

7

 supplied with the unit. (Seam taping)

5. Check for correct drainage. (Fig. 5-3)

Fill the drain pan with water of about 1 L from the tubing sensor access port.

After checking for correct drainage, replace the tubing sensor access port cover.

3.

B

1.

D

2.

C

4.

E

B

C

D

A

E

F

Fig. 5-2

Fig. 5-3

1

2    3

L

1

N

2

G

K

F

J

I

H

E

D

C

B

A

6-1. Electric wiring (Fig. 6-1)

Wiring procedures

1. Remove the (two) tapping screws then remove the electric part cover.
2. Connect the electric wires securely to the corresponding terminals.
3. Replace the removed parts.
4. Tie the electric wires with the local wiring clamp located in the right side of the

junction box.

A

Cover

B

Set screws

C

Beam

D

Wiring clamp

E

Power supply board

F

Control board

G

Wire service entrance

H

Terminal block for indoor and outdoor units connection

I

Terminal block for electric heater power supply (for only PCH models)

J

Terminal block for remote controller

K

Grounding cable connector

Fig. 6-1

6. Electrical work

A

Drain pan

B

Drain tubing

C

Socket cover 

6

D

Joint socket 

5

E

Drain tubing cover 

7

F

Drain tubing sensor

*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. A 10 m wire is attached in the remote controller accessory.
*3. The figures are NOT always against the ground.

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer and thicker than other cables.

Indoor unit model
Indoor unit power supply (Heater)
Indoor unit input capacity (Heater)

*1

Main switch (Breaker)

Indoor unit power supply (Heater)
Indoor unit power supply (Heater) earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit

*2

Indoor unit (Heater) L-N

*3

Indoor unit-Outdoor unit S1-S2

*3

Indoor unit-Outdoor unit S2-S3

*3

Remote controller-Indoor unit

*3

Wiring

Wire No. 

×

 size

(mm

2

)

Circuit

rating

PCA

PCH

~/N (single), 50Hz, 220-230-240V

16A

×

 Min. 1.5

×

 Min. 1.5

×

 2.5 (Polar)

×

 2.5 (Polar)

×

 Min. 2.5

×

 Min. 2.5

×

 0.69 (Non-polar)

×

 0.69 (Non-polar)

AC 220-230-240V

AC 220-230-240V

AC 220-230-240V

DC24V

DC24V

DC14V

DC14V

Содержание Mr. Slim PCA-RP-GA

Страница 1: ...ndizionatore d aria MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î È ÛˆÛÙ Ú ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este...

Страница 2: ...e If combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not insta...

Страница 3: ...outdoor unit installation manual 1 2 3 4 5 6 7 Fig 3 1 Fig 3 2 Fig 3 3 E D H C W A B U N IT 3 2 Preparation for installation Fig 3 2 3 2 1 Suspension bolt installing spacing mm Models A B C RP2 933 1000 221 RP2 5 3 1240 1310 221 RP4 1240 1310 281 RP5 6 1547 1620 281 3 2 2 Refrigerant and drain tubing location mm Models D E F G H J K L RP2 2 5 3 131 175 178 90 82 159 156 90 RP4 5 6 191 235 238 150 ...

Страница 4: ...t Fig 3 6 Installing procedures 1 Install the washer 1 supplied with the unit and the nut to be locally procured 2 Set hook the unit through the suspending bolts 3 Tighten the nuts Check the unit installing condition Check that the unit is horizontal between the right and left sides Check that the unit slopes continuously downward from the front to the rear When embedding pipes into the wall 2 Ins...

Страница 5: ... 2 ø12 7 16 2 16 6 ø15 88 19 3 19 7 ø19 05 23 6 24 0 Copper pipe O D Flare nut O D Tightening torque mm mm N m ø6 35 17 14 18 ø6 35 22 34 42 ø9 52 22 34 42 ø12 7 26 49 61 ø12 7 29 68 82 ø15 88 29 68 82 ø15 88 36 100 120 ø19 05 36 100 120 1 The flare nut is attached to its pipe 2 The flare nut is in the outdoor unit accessory Do not use the flare nut attached If it is used a gas leakage or even a p...

Страница 6: ... Grounding cable connector Fig 6 1 6 Electrical work A Drain pan B Drain tubing C Socket cover 6 D Joint socket 5 E Drain tubing cover 7 F Drain tubing sensor 1 A breaker with at least 3 mm contact separation in each pole shall be provided Use non fuse breaker NF or earth leakage breaker NV 2 A 10 m wire is attached in the remote controller accessory 3 The figures are NOT always against the ground...

Страница 7: ... is restored after a power failure when a Program timer is connected select Timer mode Normally on Timer mode on Fig 6 2 Fig 6 4 SW No 3 SW contents Main Cooling heating display in AUTO mode ON OFF Comment When you do not want to display Cooling and Heating in the Auto mode set to No Yes No SW No 4 SW contents Main Intake temperature display ON OFF Comment When you do not want to display the intak...

Страница 8: ...he control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Ω Ω Ω Ω Insulation resistance 7 2 Test run The following 3 methods are available 7 2 1 Using wired remote controller Fig 7 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode s...

Страница 9: ...n lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possible due to ...

Страница 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U334H01 The product at hand is based on the following EU regulations ...