5
Model name
Indoor unit
PEAD-RP71EA
PEAD-RP100EA2
PEAD-RP125EA PEAD-RP140EA
Outdoor unit
PUH-P71VHA
PUH-P71YHA PUH-P100VHA PUH-P100YHA PUH-P125YHA PUH-P140YHA
Cooling
Capacity
Btu/h
27,000
34,100
42,000
48,500
kW
7.9
10.0
12.3
14.2
Total input
kW
2.97
3.69
4.41
5.63
EER
2.66
2.71
2.79
2.52
Energy label class
D
D
D
E
SHF
0.83
0.86
0.82
0.83
Heating
Capacity
Btu/h
30,700 [37,300]
39,200 [46,800]
48,800 [58,200] 57,000 [66,400]
kW
9.0 [10.93]
11.5 [13.71]
14.3 [17.06]
16.7 [19.46]
Total input
kW
3.11 [5.04]
3.42 [5.63]
4.32 [7.08]
5.28 [8.04]
COP
2.89
3.36
3.31
3.16
Energy label class
D
C
C
D
Booster heater
kW
[2.1]
[2.4]
[3.0]
[3.0]
Power supply
Phase
[
1
1
3
3
Cycle
Hz
50
50
50
50
Voltage
V
230
230
400
400
Breaker size
A
32
16
32
16
25
Indoor unit
Air flow
CMM
20-25
33.5-42
33.5-42
36.5-46
(Low-High)
CFM
706-883
1183-1483
1183-1483
1288-1624
External pressure
Pa
70(130)
70(130)
70(130)
Sound level
dB(A)
37-41
44-50
44-50
46-51
(Low-High)
(130Pa : 40-45)
(130Pa : 46-52)
(130Pa : 46-52) (130Pa : 47-53)
External finish
Galvanized sheets
Dimension
W : mm
1175
1415
1415
1715
D : mm
740
740
740
H : mm
295
325
325
W : inch
46-1/8
55-11/16
55-11/16
67-1/2
D : inch
27-5/8
29-1/8
29-1/8
H : inch
11-5/8
12-13/16
12-13/16
Weight
kg
44 [46]
65 [68]
65 [68]
70 [73]
lbs
97 [101]
143 [150]
143 [150]
154 [161]
Unit drain pipe
R1(External thread)
Outdoor unit
Air flow
CMM
55
65
100
CFM
1,940
2,290
3,530
Sound level at cooling
dB(A)
49
50
50
51
Sound level at heating
dB(A)
50
52
52
53
External finish
Ivory Munsell 5Y 7/1
Dimension
W : mm
950
950
950
D : mm
330+30
330+30
330+30
H : mm
943
943
1350
W : inch
37-3/8
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
37-1/8
53-1/8
Weight
kg
93
94
131
lbs
205
207
289
Refrigerant pipe size
Gas side O.D.
mm
15.88
15.88
15.88
inch
5/8
5/8
5/8
Liquid side O.D.
mm
9.52
9.52
9.52
inch
3/8
3/8
3/8
Refrigerant pipe length Height difference
m
Max. 30
Max. 30
Max. 30
Length
m
Max. 50
Max. 50
Max. 50
2-2. CEILING-CONCEALED TYPE
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor : D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Heating Indoor : D.B. 20
:
(68˚F)
Outdoor : D.B. 7
:
(45˚F) W.B. 6
:
(43˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46
:
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5
:
w
Heating
Upper limit D.B. 28˚C
D.B. 21
:
, W.B. 15˚C
Lower limit D.B. 17˚C
D.B. -11
:
, W.B. -12˚C
4. Above data based on indicated voltage
w
If optional Air protect guide installed. D.B.-15
:
Indoor unit
Single phase 230V 50Hz
Single phase 230V 50Hz
/ 3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3 phase
OCS07-1.qxp 06.3.22 3:39 PM Page 5
Содержание Mr.Slim PCA-RP GA
Страница 34: ...34 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Страница 35: ...35 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Страница 57: ...57 9 2 PLA RP AA PLA RP AA2 9 2 1 FRESH AIR INTAKE AMOUNT ...
Страница 58: ...58 9 2 2 BRANCH DUCT Installation at site ...
Страница 68: ...68 PEAD RP60GA PEAD RP71GA ...
Страница 69: ...69 PEAD RP100GA ...
Страница 74: ...74 ...