13
)RUZLUHOHVVUHPRWHFRQWUROOHU)LJ
Changing the power voltage setting
%HVXUHWRFKDQJHWKHSRZHUYROWDJHVHWWLQJGHSHQGLQJRQWKHYROWDJHXVHG
1
Going to the function select mode
Press
the
CHECK
button
F
twice continuously.
6WDUWWKLVRSHUDWLRQIURPWKHVWDWXVRIUHPRWHFRQWUROOHUGLVSOD\WXUQHGRII
CHECK
is lit and “00” blinks.
Press
the temp button
C
once to set “50”. Direct the wireless remote controller
toward the receiver of the indoor unit and press the
h
button
A
.
2
Setting the unit number
Press
the
temp buttons
C
and
D
to set the unit number “00”. Direct the
wireless remote controller toward the receiver of the indoor unit and press the
min
button
B
.
3
Selecting a mode
Enter 04 to change the power voltage setting using the
temp buttons
C
and
D
. Direct the wireless remote controller toward the receiver of the indoor unit and
press the
h
button
A
.
&XUUHQWVHWWLQJQXPEHU
EHHSVHFRQG
EHHSVVHFRQGHDFK
EHHSVVHFRQGHDFK
4
Selecting the setting number
Use
the
temp buttons
C
and
D
to change the power voltage setting to 01
9'LUHFWWKHZLUHOHVVUHPRWHFRQWUROOHUWRZDUGWKHVHQVRURIWKHLQGRRUXQLW
and press the
h
button
A
.
5
To select multiple functions continuously
Repeat
steps
3
and
4
to change multiple function settings continuously.
6
Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and press
the
button
E
.
Note:
Whenever changes are made to the function settings after installation or main
WHQDQFHEHVXUHWRUHFRUGWKHFKDQJHVZLWKDPDUNLQWKH³6HWWLQJ´FROXPQRI
the Function table.
6. Electrical work
6.3.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
Function table
Select unit number 00
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Power failure automatic recovery
Not available
01
1
Available
w
2
ȅ
Indoor temperature detecting
Indoor unit operating average
02
1
ȅ
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
ȅ
6XSSRUWHGLQGRRUXQLWLVQRWHTXLSSHGZLWKRXWGRRUDLULQWDNH
2
6XSSRUWHGLQGRRUXQLWLVHTXLSSHGZLWKRXWGRRUDLULQWDNH
3
Power voltage
240 V
04
1
220 V, 230 V
2
ȅ
6HOHFWXQLWQXPEHUVWRRUDOOXQLWV$/>ZLUHGUHPRWHFRQWUROOHU@>ZLUHOHVVUHPRWHFRQWUROOHU@
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Filter sign
100 Hr
07
1
2500 Hr
2
ȅ
1R¿OWHUVLJQLQGLFDWRU
3
Fan speed
Silent
08
1
Standard
2
ȅ
High ceiling
3
,QVWDOOHGRSWLRQVKLJKHI¿FLHQF\¿OWHU
Not supported
10
1
ȅ
Supported
2
Up/down vane setting
No vanes
11
1
Equipped with vanes (vanes angle setup
1
2
ȅ
Equipped with vanes (vanes angle setup
2
3
Fan speed during the cooling thermostat is OFF
Setting fan speed
27
1
Stop
2
Extra low
3
ȅ
w
When the power supply returns, the air conditioner will start 3 minutes later.
CHECK
CHECK
ON/OFF
TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESET
SET
CLOCK
CHECK
CHECK
CHECK
)LJ