12
en
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer)
Indicates whether control power is supplied. Make sure that this LED is always lit.
LED 2 (power for remote controller)
Indicates whether power is supplied to the remote controller. This LED lights only
in the case of the indoor unit which is connected to the outdoor unit refrigerant ad-
dress “0”.
LED 3 (communication between indoor and outdoor units)
Indicates state of communication between the indoor and outdoor units. Make sure
that this LED is always blinking.
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Check code
Symptom
Remark
E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
For details, check the LED
display of the outdoor control-
ler board.
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
U2
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1, Ud
Abnormal high pressure (63H worked)/Overheating safeguard operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan safeguard stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal synchronous
signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
7. Test run
• On wired remote controller
Check code displayed in the LCD.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Symptom
Cause
Wired remote controller
LED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
For about 3
minutes following
power-on
After LED 1, 2 are lighted, LED 2 is turned
off, then only LED 1 is lighted. (Correct
operation)
• For about 3 minutes following power-on, operation of the
remote controller is not possible due to system start-up.
(Correct operation)
PLEASE WAIT
→
Error code
After about 3
minutes has
expired following
power-on
Only LED 1 is lighted.
→
LED 1, 2 blink.
• Connector for the outdoor unit’s protection device is not
connected.
• Reverse or open phase wiring for the outdoor unit’s power
terminal block (L1, L2, L3)
Display messages do not appear even
when operation switch is turned ON
(operation lamp does not light up).
Only LED 1 is lighted.
→
LED 1 blinks twice,
LED 2 blinks once.
• Incorrect wiring between indoor and outdoor units (incorrect
polarity of S1, S2, S3)
• Remote controller wire short
RG79F453H01_en.indd 12
2019/06/25 11:12:18
Содержание Mr.Slim PCA-M-HA Series
Страница 159: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...