22
10-5. HOW TO CHECK THE PARTS
PCA-A24GA
PCA-A30GA
PCA-A36GA
PCA-A42GA
PCA-A24GA
1
PCA-A30GA
1
PCA-A36GA
1
PCA-A42GA
1
PCA-A24GA
2
PCA-A30GA
2
PCA-A36GA
2
PCA-A42GA
2
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
4
5
2
3 6 1
Orange
Red
Pink
Yellow Brown Blue
M
4
2
5
3
1
Pink
Orange
Red
Yellow
Blue
M
OFF : 130
i
5
:
ON : 80
i
20
:
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
:
(50˚F)~30
:
(86˚F))
(Refer to Thermistor Characteristic graph.)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Normal
4.3k
"
~9.6k
"
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(Winding temperature 20
:
(68˚F))
Fan motor (MF)
Abnormal
Open or short
Motor terminal
or
Relay connector
60.8
"
55.1
"
41.1
"
54.3
"
Normal
Open or short
Abnormal
Connector
PCA-A24·30GA
(1)(2)
140~160
"
Normal
Open or short
Abnormal
Connector
PCA-A36·42GA
(1)(2)
Normal
Vane motor (MV)
140~160
"
Red–Yellow
Red–Blue
Red–Blue
Red–Pink
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Red–Black
White–Black
PCA-A24GA
(1)(2)
PCA-A30GA
(1)(2)
PCA-A36GA
(1)(2)
PCA-A42GA
(1)(2)
3. Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
· the outdoor unit malfunctions.
· the indoor fan malfunctions.
(2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control
or temperature control etc. does not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is acti-
vated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum. (The indoor unit heat exchanger may freeze.)
(5) After emergency operation has been deactivated, set the switches etc. to their original positions.
(6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position.