68
Model
Max. height
difference
Additional refrigerant charging amount (kg/oz)
A12, A18
30 m, 100 ft
30 m, 100 ft
0
–
–
–
–
–
–
–
0.06 kg 0.11 kg 0.17 kg
2 oz
4 oz
6 oz
A24, A30, A36
50 m, 165 ft
30 m, 100 ft
0
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 1.36 kg 1.53 kg 1.70 kg
6 oz
12 oz
18 oz
24 oz
30 oz
36 oz
42 oz
48 oz
54 oz
60 oz
A42
50 m, 16 5 ft
30 m, 100 ft
0
0
0
0
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg
6 oz
12 oz
18 oz
24 oz
30 oz
36 oz
42 oz
Max. pipe
length
20 m
25 m
27 m
30 m
33.5 m 36.6 m
40 m
43 m
45.5 m 48.8 m
50 m
70 ft
80 ft
90 ft
100 ft
110 ft
120 ft
130 ft
140 ft
150 ft
160 ft
165 ft
9-1-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 20 m(70 ft) for A12-A36 or 30 m(100 ft) for A42.
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the
permitted pipe lengths in the chart below.
*
When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation perform
ance.