27
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
10-3. TROUBLESHOOTING CHECK TABLE
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
No. Symptom
Indication
Abnormal point / Condition
Condition
Correspondence
LED1
(Red)
LED2
(Yellow)
1
Outdoor
unit does
not oper-
ate.
Lightning Twice
Outdoor power system
IPM protection stop or lock protection stop is continuously
performed three times within 1 minute after the compressor
gets started, or converter protection stop or bus-bar voltage
protection stop is continuously performed 3 times within 3
minutes after start-up.
Check the connection of the compressor connect-
ing wire.
Refer to 10-5. "How to check inverter/compres-
sor".
Refer to 10-5. "Check of compressor start failure".
Check the stop valve.
•
•
•
•
2
Lightning 3
times
Discharge temperature therm-
istor
A short circuit is detected in the thermistor during opera-
tion, or an open circuit is detected in the thermistor after 10
minutes of compressor start-up.
Refer to 10-5. "Check of outdoor thermistor".
•
3
Lightning 4
times
Fin temperature thermistor
A short or open circuit is detected in the thermistor during
operation.
Refer to 10-5. "Check of outdoor thermistor".
•
P.C. board temperature therm-
istor
Replace the outdoor electronic control P.C. board.
•
4
Lightning 5
times
Ambient temperature thermis-
tor
A short or open circuit is detected in the thermistor during
operation.
Refer to 10-5. "Check of outdoor thermistor".
•
Outdoor heat exchanger
temperature thermistor
A short circuit is detected in the thermistor during operation,
or an open circuit is detected in the thermistor after 5 minutes
(in cooling) and 10 minutes (in heating (MUZ)) of compressor
start-up.
Defrost thermistor (MUZ)
A short circuit is detected in the thermistor during operation,
or an open circuit is detected in the thermistor after 5 minutes
of compressor start-up.
5
Lightning 6 times
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Refer to 10-5. "How to check miswiring and serial
signal error.
•
6
Lightning 7 times
Nonvolatile memory data
The nonvolatile memory data cannot be read properly.
Replace the outdoor electronic control P.C. board.
•
7
Lightning 8 times
Current sensor
Current sensor protection stop is continuously performed
twice.
Replace the power board.
•
8
Lightning 11
times
Communication error between
P.C. boards
The communication protection stop between boards is con-
tinuously performed twice.
Check the connecting wire between outdoor elec-
tronic control P.C. board and power board.
•
9
Lightning 12 times Zero cross detecting circuit
The protection stop of the zero cross detecting circuit is
continuously performed 10 times.
Check the connecting wire among outdoor elec-
tronic control P.C. board, noise
fi
lter P.C. board and
power board.
•
10
'Outdoor
unit stops
and restarts
3 minutes
later' is
repeated.
Twice Goes
out
IPM protection
Overcurrent is detected after 30 minutes of compressor start-
up.
Reconnect compressor connector.
Refer to 10-5. "How to check inverter/compres-
sor".
Refer to 10-5. "Check of compressor start failure".
Check the stop valve.
Check the power module (PAM module).
•
•
•
•
•
Lock protection
Overcurrent is detected within 30 minutes of compressor
start-up
11
3 times
Goes out
Discharge temperature protec-
tion
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart
if discharge temperature thermistor reads 212°F (100°C) or
less 3 minutes later.
Check the amount of gas and refrigerant circuit.
Refer to 10-5. "Check of LEV".
•
•
12
4 times
Goes out
Fin temperature protection
The
fi
n temperature exceeds 189°F (87°C) during operation. • Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5. "Check of outdoor fan motor".
P.C. board temperature pro-
tection
The P.C. board temperature exceeds 158°F (70°C) during
operation.
13
5 times
Goes out High-pressure protection
The outdoor heat exchanger temperature exceeds 158°F (70
°C) during cooling or indoor gas pipe temperature exceeds
158°F (70°C) during heating (MUZ).
Check around of gas and the refrigerant circuit.
Check of stop valve.
•
•
14
8 times
Goes out Converter protection
A failure is detected in the operation of the converter during
operation.
Replace the power board.
•
15
9 times
Goes out
Bus-bar voltage protection (1)
The bus-bar voltage exceeds 400 V or falls to 200 V or below
during compressor operating.
• Check the voltage of power supply.
• Replace the power board or the outdoor electronic
control P.C. board.
• Refer to 10-5. "Check of bus-bar voltage".
Bus-bar voltage protection (2)
The bus-bar voltage exceeds 400 V or falls to 50 V or below
during compressor operating.
16
13 times Goes out Outdoor fan motor
Failure occurs continuously three times within 30 seconds
after the fan gets started.
Refer to 10-5. "Check of outdoor fan motor".
•
17
Lighting
8 times
Current sensor protection
A short or open circuit is detected in the current sensor during
compressor operating.
Replace the power board.
•
18
Lighting 11
times
Communication between P.C.
boards protection
Communication error occurs between the outdoor electronic
control P.C. board and power board for more than 10 sec-
onds.
Check the connecting wire between outdoor elec-
tronic control P.C. board and power board.
•
19
Lighting 12
times
Zero cross detecting circuit
protection
Zero cross signal cannot be detected while the compressor is
operating.
Check the connecting wire among outdoor elec-
tronic control P.C. board, noise
fi
lter P.C. board and
power board.
•
NOTE
1. The location of LED is illustrated at the right figure. Refer to 10-6.1.
2. LED is lighted during normal operation.
Outdoor electronic control P.C. board (Parts side)
LED2 LED1
Lighting
→