16
8-3. HEAT ( ) OPERATION (MSZ)
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 61 ~ 88°F (16 ~ 31°C).
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-
perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-
densing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat
exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
8-4. FAN( )OPERATION (MSY)
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit does not operate.
8-5. “I FEEL CONTROL” ( ) OPERATION (MSY)
(1) Press OPERATE/STOP (ON/OFF) button on the remote controller. OPERATION INDICATOR lamp of the indoor unit
turns ON with a beep tone.
(2) Select “I FEEL CONTROL” mode with OPERATION SELECT button.
(3) The operation mode is determined by the room temperature at start-up of the operation.
• Once the mode is fixed, the mode does not change by room temperature afterwards.
• Under the ON TIMER (
) operation, mode is determined according to the room temperature at the start-up of
operation.
(4) The initial set temperature is decided by the initial room temperature.
Initial room temperature
Model
Initial set temperature
79°F (26°C) or more
COOL mode of
"I FEEL CONTROL"
75°F (24°C)
77 to 79°F (25 to 26°C)
Initial room temperature minus 4°F (2°C)
Less than 79°F (25°C)
DRY mode of
"I FEEL CONTROL"
Initial room temperature minus 4°F (2°C)
(5) TEMPERATURE buttons
In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too
warm.
Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
•
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, consider-
ing the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user's preference to
heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature does not change.
TOO
COOL
…To raise the set temperature 2~4°F (1~2°C)
TOO
WARM
…To lower the set temperature 2~4°F (1~2°C)
OBH548D