6 OPTIONS AND PERIPHERAL EQUIPMENT
6.9 Molded-case circuit breakers, fuses, magnetic contactors
171
6
■
For main circuit power supply [WG]
• MR-J5W2-_G
*1 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*2 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
• MR-J5W3-_G
*1 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*2 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
Total output of
rotary servo
motors
Total
continuous
thrust of linear
servo motors
Total output of
direct drive
motors
Molded-case circuit breaker
Fuse
Frame,
rated current
Voltage
AC [V]
Class
Current
[A]
Voltage
AC [V]
300 W or less
30 A frame 5 A
240
T
15
400
DUD-N30
Over 300 W
600 W or less
150 N or less
100 W or less
30 A frame 10 A
20
Over 600 W
1 kW or less
Over 150 N
300 N or less
Over 100 W
252 W or less
30 A frame 15 A
20
Over 1 kW
2 kW or less
Over 300 N
720 N or less
Over 252 W
838 W or less
30 A frame 20 A
30
Total output of
rotary servo
motors
Total
continuous
thrust of linear
servo motors
Total output of
direct drive
motors
Molded-case circuit breaker
Fuse
Frame,
rated current
Voltage
AC [V]
Class
Current
[A]
Voltage
AC [V]
450 W or less
150 N or less
30 A frame 10A
240
T
20
400
DUD-N30
Over 450 W
800 W or less
Over 150 N
300 N or less
252 W or less
30 A frame 15 A
20
Over 800 W
1.5 kW or less
Over 300 N
450 N or less
Over 252 W
378 W or less
30 A frame 20 A
30