170
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.9 Molded-case circuit breakers, fuses, magnetic contactors
For control circuit power supply
When the wiring for the control circuit power supply (L11/L21) is thinner than that for the main circuit power supply (L1/L2/L3),
install an overcurrent protection device (molded-case circuit breaker, fuse, etc.) to protect the branch circuit.
*1 When having the servo amplifier comply with the IEC/EN/UL/CSA standard, refer to "Compliance with global standards" in the following
user's manuals.
MR-J5-G/MR-J5W-G User's Manual (Introduction)
MR-J5-A User's Manual (Introduction)
When using the servo amplifier with the DC power supply input
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.
■
For main circuit power supply [G] [A]
*1 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
*2 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
Servo amplifier
Molded-case circuit breaker
Fuse (Class T)
Fuse (Class K5)
Frame, rated
current
Voltage AC [V]
Current [A]
Voltage AC [V]
Current [A]
Voltage AC [V]
MR-J5-10_
30 A frame 5 A
240
1
300
1
250
MR-J5-20_
MR-J5-40_
MR-J5-60_
MR-J5-70_
MR-J5-100_
MR-J5-200_
MR-J5-350_
MR-J5W2-22G
MR-J5W2-44G
MR-J5W2-77G
MR-J5W2-1010G
MR-J5W3-222G
MR-J5W3-444G
Servo
amplifier
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated current
Voltage AC
[V]
Class
Current [A]
Voltage DC
[V]
Power factor
improving
reactor is not
used
Power factor
improving
reactor is used
MR-J5-10_
30 A frame 5 A
30 A frame 5 A
240
T
10
400
DUD-N30
MR-J5-20_
30 A frame 5 A
30 A frame 5 A
MR-J5-40_
30 A frame 10 A
30 A frame 5 A
15
MR-J5-60_
30 A frame 15 A
30 A frame 10 A
20
MR-J5-70_
30 A frame 15 A
30 A frame 10 A
MR-J5-100_
(3-phase power
supply input)
30 A frame 15 A
30 A frame 10 A
MR-J5-100_
(1-phase power
supply input)
30 A frame 15 A
30 A frame 15 A
30
MR-J5-200_
30 A frame 20 A
30 A frame 20 A
40
MR-J5-350_
30 A frame 30 A
30 A frame 30 A
70