44
1. OUTLINE
1.4 Connection and parameter setting
NOTE
• Always reset the inverter after making the setting of the parameters. After you have changed the communication-related
parameters, communication cannot be established until the inverter reset.
• Avoid simultaneous access from multiple devices. Otherwise, a communication error (error code: 0x80010003, 0x80010101,
or 0x80010102) may occur.
1.4.6
Connection of inverter via Ethernet (CC-Link IE
TSN communication)
The inverter can be connected to a personal computer via the Ethernet port of the inverter (FR-A800/FR-F800 with FR-A8NCG
in it, FR-E800-(SC)EPA, or FR-E800-(SC)EPB).
833
Ethernet function selection 1
31
0, 10, 20, 30 to
32, 36 to 38,
9999
Set the application, protocol, etc.
834
Ethernet function selection 2
20
835
Ethernet function selection 3
9999
837
Ethernet IP filter address 1
0
0 to 255
Set the range of connectable IP addresses for the network
devices. (When
Pr.837 to Pr.840
= "0 (initial value)", the
function is disabled.)
838
Ethernet IP filter address 2
0
0 to 255
839
Ethernet IP filter address 3
0
0 to 255
840
Ethernet IP filter address 4
0
0 to 255
841
Ethernet IP filter address 2 range
specification
9999
0 to 255, 9999
842
Ethernet IP filter address 3 range
specification
9999
0 to 255, 9999
843
Ethernet IP filter address 4 range
specification
9999
0 to 255, 9999
844
Ethernet command source selection
IP address 1
0
0 to 255
To limit the network devices that send the operation or
speed command through the Ethernet network (MODBUS/
TCP or CC-Link IE Field Network Basic), set the range of IP
addresses of the devices. When
Pr.844 to Pr.847
= "0
(initial value)", no IP address is specified for sending
commands through the Ethernet network. In this case,
operation through the Ethernet network (MODBUS/TCP or
CC-Link IE Field Network Basic) is not available. When four
or more clients attempt a connection to the inverter during
MODBUS/TCP communication, the connection attempted
from outside of the IP address range set for Ethernet
command source selection may be forcibly closed.
845
Ethernet command source selection
IP address 2
0
0 to 255
846
Ethernet command source selection
IP address 3
0
0 to 255
847
Ethernet command source selection
IP address 4
0
0 to 255
848
Ethernet command source selection
IP address 3 range specification
9999
0 to 255, 9999
849
Ethernet command source selection
IP address 4 range specification
9999
0 to 255, 9999
850
Ethernet TCP disconnection time
coefficient
3600
1 to 7200
When the inverter does not receive a packet within the time
calculated by multiplying the Pr.850 setting by 8 in seconds
from the devices with the TCP connection established, the
connection will be forcibly closed.
851
Ethernet signal loss detection
function selection
3
0
Signal loss detection
disabled
Set the availability of the signal loss
detection and select the action when
Ethernet communication is
interrupted by physical factors.
2
The alarm (LF)
signal is output for a
signal loss.
3
A protective function
(E.OP1) is activated
for a signal loss.
852
Ethernet communication check time
interval
1.5 s
0
Ethernet communication is available, but the inverter output
is shut off in the NET operation mode.
0.1 to 999.8 s
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (
Pr.844 to
Pr.849
). If a no-communication state persists for the
permissible time or longer, the inverter output is shut off.
9999
No communication check (signal loss detection)
Pr.
Name
Initial
value
Setting range
Description