3. FUNCTION
3.14 Firmware update
1
2
3
4
5
6
7
8
9
10
3.14.8 Error codes for Firmware Update Tool
Error code
Error message
Countermeasure
1000
[Invalid Windows version]
This application works on computers with Windows
10 or later.
Use computers with Windows 10 or later.
1001
[Invalid .Net Framework version]
Please install .Net Framework v4.5 or later.
Install .Net Framework v4.5 or later.
1003
[Error]
The required file is not found.
The required file is not found.
Reinstall FR Configurator2.
1004
[Invalid file name]
The VFD firmware was not found.
Check that the firmware file is in the folder specified in "Select
VFD firmware" section.
1005
[Error]
The application cannot start up on a 32-bit
operating system.
Use a 64-bit operating system.
2000 to 2800
[Invalid VFD firmware]
The VFD firmware cannot be read correctly.
The firmware file may be damaged.
Download the firmware file from the Mitsubishi Electric FA
Global Website again.
3000
[No Ethernet adapter]
The Ethernet adapter was not found.
Check that the inverters are connected via Ethernet and the
power of the inverters are ON.
Scan the network after selecting the adapter.
4000
[Network scan]
The VFD was not found on the network.
Check that the power of the inverters are ON.
Check that the inverters are connected via Ethernet.
Check that "5001" and "45237" are set in any two parameters
from
Pr.1427 to Pr.1430 Ethernet function selection
.
5000
[Invalid target]
The target VFD is not selected.
Select the inverters whose firmware are to be updated, and
perform firmware update.
7000
This VFD is not supported.
Firmware Update Tool is not available for a selected inverter.
When "Err" is displayed on the operation panel or an inverter
does not start up properly, turn OFF and then ON the power.
8000 to 8A01
Failed to update.
An error occurred during the update. Check the following points
and perform the update again.
· Check if the inverter's power is OFF.
· Check for a break in the USB/Ethernet cable.
· When the firmware of inverters having addresses in different
networks are to be updated, check that the settings of
Pr.442 to
Pr.445 Default gateway address
are correct.
· Download the firmware file again as it may be damaged.
9000
Failed to clear the alarm history.
An error occurred while clearing the fault history after the
firmware update. Clear the fault history in the inverter manually.
9001
Failed to clear all parameter settings.
An error occurred during All parameter clear after the firmware
update. Perform All parameter clear in the inverter manually.