232
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.11 Power factor improving DC reactor
*1 Use this for grounding.
*2 When using the power factor improving DC reactor, remove the short-circuit bar between P3 and P4.
*3 Maximum dimensions. The dimensions vary depending on the curvature of the input/output lines.
*4 Selection requirements for the wire size are as follows.
Wire type: 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Construction requirements: Single wire set in midair
Servo amplifier
Power factor
improving
DC reactor
Dimensions [mm]
Terminal
size
Mass
[kg]
Wire [mm
2
W
W1
H
D
D1
D2
D3
d
MR-J5-200_
FR-HEL-3.7K
77
55
92
82
66
57
37
M4
M4
1.5
2 (AWG 14)
MR-J5-350_
FR-HEL-7.5K
86
60
113
98
81
72
43
M4
M5
2.5
3.5 (AWG 12)
MR-J5-500_
FR-HEL-11K
105
64
133
112
92
79
47
M6
M6
3.3
5.5 (AWG 10)
MR-J5-700_
FR-HEL-15K
105
64
133
115
97
84
48.5
M6
M6
4.1
8 (AWG 8)
W ± 2
W1
H
D1
D3
D2
P P1
*2
P3
P4
FR-HEL
P1
P
4-d mounting hole
(Varnish is removed only from bottom right (face and back side))
*1
D or less
Servo amplifier
5 m or less
Содержание MELSERVO-J5 MR-J5-G Series
Страница 1: ...MR J5 User s Manual Hardware MR J5 _G_ MR J5W_ _G_ MR J5 _A_ Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 473: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 471 12 MEMO ...
Страница 477: ......