3 SPECIFICATIONS
3.1 General Specifications
35
3
3
SPECIFICATIONS
This chapter explains general and performance specifications of CC-Link IE Field Network board.
3.1
General Specifications
General specifications of CC-Link IE Field Network board are shown below.
*1 Do not use or store the board under the environment where the atmospheric pressure is higher than the one at the altitude of 0 m. Doing
so may cause a malfunction.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
The general specifications both CC-Link IE Field Network board and a personal computer must be satisfied
after installation.
Item
Specification
Operating ambient temperature
0 to 55
Storage ambient temperature
-25 to 75
Operating ambient humidity
5 to 95% RH, non-condensing
Storage ambient humidity
Vibration resistance
Compliant
with JIS B
3502 and IEC
61131-2
Frequency
Constant
acceleration
Half amplitude
Sweep count
Under
intermittent
vibration
5 to 8.4 Hz
3.5 mm
10 times each in X, Y,
and Z directions
8.4 to 150 Hz
9.8 m/
Under
continuous
vibration
5 to 8.4 Hz
1.75 mm
8.4 to 150 Hz
4.9 m/
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147 m/
, 3 times each in X, Y, and Z directions)
Operating atmosphere
No corrosive gases
Operating altitude
0 to 2000 m
Installation location
Inside a control panel
Overvoltage category
II or less
Pollution degree
2 or less
Содержание MELSEC Q80BD-J71GF11-T2
Страница 2: ......
Страница 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 118: ...116 12 MONITORING MEMO ...
Страница 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Страница 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Страница 243: ...241 I U Utility 83 ...
Страница 247: ......