Error codes
Error code list
Error code
Description
10 (Decimal)
The specified target channel is not valid. The target channel is not within the range of the
number of channels of the mounted module. Please try again after confirming the setting.
Labels
Input labels
Name (Comment)
Label name
Data
type
Setting range
Description
Execution
command
FB_EN
Bit
ON, OFF
ON: The FB is activated.
OFF: The FB is not activated.
Module start XY
address
i_Start_IO_No
Word
Depends on the I/O point
range. For details, refer to
the CPU user's manual.
Specify the starting XY
address (in hexadecimal)
where the Q64DA module is
mounted. (For example, enter
H10 for X10.)
Channel No.
i_CH
Word
1~4
Specify the channel number.
Offset adjustment
amount
i_Adjust_Amoun
t
Word
-3000~3000
Set the offset adjustment
amount of the specified
channel.
Setting value
change command
i_Value_Change
Bit
ON, OFF
Turn ON to change the D/A
output.
Turn OFF after changing the
output.
User range write
command
i_Write_Offset
Bit
ON, OFF
Turn ON to write the adjusted
offset value to the flash
memory.
Turn OFF after writing is
completed.
MELSEC-Q Digital-Analog Converter Module FB Library Reference Manual
FBM-M042-B