6
-
26
6.7 Q Series-compatible Module Input Response Time Selection (I/O
Response Time)
(1) Definition
This function changes the input response time for each Q series-compatible module.
shows the modules available for input response time change and selectable time settings.
The Q series-compatible modules in the table above take in external inputs within the set time here.
Table6.8 Modules available for input response time change
Module name
Type
Settable time setting
Input module
“Input”
1ms, 5ms, 10ms, 20ms, 70ms
(Default: 10ms)
I/O combined module
“I/O Mix”
High-speed input module
“Hi Input”
0.1ms, 0.2ms, 0.4ms, 0.6ms, 1ms
(Default: 0.2ms)
Interrupt module
“Interrupt”
Figure 6.21 Input response time
OFF
OFF
ON
ON
External input
Q series-compatible module
Input response time