Appendix
QE81WH4W
■
Voltage transform unit
Item Specification
Model QE8WH4VT
Phase wire system
Three-phase 4-wire
Input voltage range
63.5/110 to 277/480 V AC (The product does not operate on the voltage
below 55/95 V AC.)
Frequency
50 Hz/60 Hz
Voltage output tolerance
±1.0% (against the rated primary voltage)
Measurement category
III
Pollution degree
II
Maximum number of
connections
5 modules
Operating
temperature
0ºC to +55ºC (Average daily temperature 35ºC or below)
Operating
humidity
5% to 95% RH (without condensation)
Storage
temperature
-25ºC to +75ºC
Operating
condition
Altitude
2000 m or lower
Commercial frequency
withstand voltage
Between voltage input terminals (P1, P2, P3, P0) and FG terminal: 2210 V AC 5
sec
Between voltage input terminals (P1, P2, P3, P0) and secondary output
terminals (PA, PB, PC, PD) (except for SLD terminal) 2210 V AC 5 sec
Insulation resistance
10 M
Ω
or more (500 V DC) at the same locations as above
Consumption VA
P1-P0: 2 VA, P2-P0: 0.3 VA, P3-P0: 0.3 VA (when inputting 277/480 V AC)
Installation location
Inside the control panel
Secondary wire length
5 m or less
Installation method
Installation on IEC rails, installation with screws
Weight 0.3kg
Product life expectancy
10 years (used under the operating conditions above.)
CE marking compliance
EN 61131-2, EN 61010-1, EN 61326-1
Combined device for CE
marking compliance
Compliant with CE when combined with the energy measuring module of
Mitsubishi general-purpose sequencer MELSEC-Q series.
Combined device for
UL/c-UL compliance
Compliant with UL/c-UL when combined with the energy measuring module
of Mitsubishi general-purpose sequencer MELSEC-Q series.
Appendix - 3