1 FUNCTIONS
1.1 Input Function
29
1
Clearing the number of input ON times
The number of input ON times can be cleared with 'Number of input ON times value clear request' (Un\G3584).
Each bit of 'Number of input ON times value clear request' (Un\G3584) corresponds to each input.
When the bit corresponding to the input to be cleared is changed from 0 (Not requested) to 1 (Requested), the value of
'Number of input ON times' (Un\G2848 to Un\G2879) is cleared and 1 (Completed) is stored in 'Number of input ON times
value clear completed' (Un\G2880).
Even if 1 (Completed) is stored in 'Number of input ON times value clear completed' (Un\G2880), the bit of 'Number of input
ON times value clear request' (Un\G3584) is not automatically changed to 0 (Not requested). Set 0 (Not requested) in
'Number of input ON times value clear request' (Un\G3584) with a program.
When 0 (Not requested) is stored in 'Number of input ON times value clear request' (Un\G3584), the bit of 'Number of input
ON times value clear completed' (Un\G2880) is changed to 0 (Not completed).
For each bit of 'Number of input ON times value clear request' (Un\G3584) and the input to be cleared, refer to the following.
Page 113 Number of input ON times value clear request
Setting procedure
Set the following items from "Application setting".
• "Input ON Number Count Function enable/disable" (
Page 98 Number of input ON times integration function enable/
• "Number of input ON times alarm detect count setting" (
Page 99 Number of input ON times alarm detection count
• "Number of input ON times alarm detect setting" (
Page 98 Number of input ON times alarm detection setting)
[Navigation window]
[Parameter]
[Module Information]
Target module
[Module Parameter]
[Application
setting]
: Performed by the input module with diagnostic functions.
0
100
0
1
0
1
0
0
1
'Number of input ON times
value clear completed'(Un\G2880)
'Number of input ON times'
(Un\G2848 to Un\G2879)
'Number of input ON times
value clear request' (Un\G3584)