APPX
Appendix 3 Buffer Memory
99
A
Number of input ON times alarm detection count setting
Set the number of input ON times alarm detection count for each input.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Setting range
• The available range is 1 to 4294967295.
• The number of input ON times alarm detection count setting error (error code: 196
H) occurs in the input terminal where a
value out of the setting range has been set.
indicates the number of an I/O terminal in which the error has occurred. (
=
0H to FH)
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 for all the inputs.
Event time stamp function enable/disable
Set whether to enable or disable the event time stamp function for each input.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (Disable) for all the inputs.
Buffer memory name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Number of input ON times
alarm detection count setting
1208
1209
1210
1211
1212
1213
1214
1215
1216
1217
1218
1219
1220
1221
1222
1223
1224
1225
1226
1227
1228
1229
1230
1231
1232
1233
1234
1235
1236
1237
1238
1239
(1) 0: Disable, 1: Enable
Buffer memory name
X0 to XF
Event time stamp function enable/disable
1248
X00
(1)
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15