11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1253
11
■
Variation rate & upper/lower limiter (7)
The variation rate and upper/lower limits of the input value (E1) are checked, and the data after the processing and an alarm
are output.
Variation rate limiter processing performs the following operations, and outputs the result to the output variation rate alarm
(BB5) of (d1) and the DMLA of the alarm detection (ALM).
*1 If the DMLI or ERRI of the disable alarm detection (INH) is set to 1, the output variation rate alarm (BB5) and the DMLA of the alarm
detection (ALM) are set to 0.
Upper/lower limiter processing performs the following operations, and outputs the result to the output upper limit alarm (BB3);
output lower limit alarm (BB4); MHA and MLA of the alarm detection (ALM); and MHA2 and MLA2 of the alarm detection
(ALM2).
*2 If the MHI or ERRI of the disable alarm detection (INH) is set to 1, the output upper limit alarm (BB3) and the MHA of the alarm detection
(ALM) are set to 0.
Note that the MHA2 of the alarm detection 2 (ALM2) remains 1.
*3 If the MLI or ERRI of the disable alarm detection (INH) is set to 1, the output lower limit alarm (BB4) and the MLA of the alarm detection
(ALM) are set to 0.
Note that the MLA2 of the alarm detection 2 (ALM2) remains 1.
*4 If the specified control cycle is not reached, the MHA2 and MLA2 status of the alarm detection 2 (ALM2) are held.
■
Output conversion processing (8)
The output value (BW) is calculated from the following expression.
■
Loop stop processing (9)
The following processing is performed according to the SPA status of the alarm detection (ALM).
■
Control cycle determination (10)
If the specified control cycle is not reached, "mode determination processing (6)" is performed regarding T as MV.
If the specified control cycle is reached, "SV setting processing (1)" is performed.
Operation error
Condition
BB5, DMLA
T1
|T-MV|
DML
0
T
(T - MV) > DML
1
MV + DML
(T - MV) < -DML
1
MV - DML
Condition
BB4, MLA, MLA2
BB3, MHA, MHA2
MV
T1 > MH
0
1
MH
T1 < ML
1
0
ML
ML
T1
MH
0
0
T1
SPA status
Processing details
1
The loop stops. The following operations are performed and the instruction ends.
• The last output value (BW) is held.
• The DVLA, MHA, MLA, and DMLA of the alarm detection (ALM) are set to 0.
• The MHA2 and MLA2 of the alarm detection 2 (ALM2) are set to 0.
• The control mode (MODE) is set to MAN.
• All of the alarm bits (BB1, BB2, BB3, BB4, and BB5) are set to 0.
0
The loop runs and "control cycle determination processing (10)" is performed.
Error code
(SD0)
Description
3400H
An invalid operation (such as division by zero) is performed.
3402H
The value specified by (s1), (s2), or (d2) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
3405H
The control cycle (CT) setting is less than 0.
The execution cycle (
T) setting is less than 0.
The value divided the control cycle (CT) by the execution cycle (
T) exceeds 32767.
BW=
×MV+NMIN
100
NMAX-NMIN
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......