![Mitsubishi Electric MELSEC iQ-R-R00CPU Скачать руководство пользователя страница 530](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139530.webp)
528
31 RUNNING A SAFETY PROGRAM
31.4 Safety CPU Operating Status
31.4
Safety CPU Operating Status
The following is a list of Safety CPU operating statuses.
• RUN state
• STOP state
• PAUSE state
Operation processing based on safety CPU operating status
Operation processing based on the Safety CPU operating status is the same as that of the standard CPU. (
Operation Processing by Operating Status)
Safety communications processing based on safety CPU operating status
Safety communications processing based on the Safety CPU operating status is as follows.
*1 If the safety operation mode is TEST MODE, output is based on the output hold and clear settings when the status of network modules
(RJ71GF11-T2) for which safety communication settings are specified is CPU STOP. (
Manual for network module used)
*2 Safety communications are not performed if a stop error occurs at the Safety CPU.
Operation processing when operating status of the Safety CPU
changes
This displays operation processing with the safety program when the operating status of the Safety CPU is changed.
*1 Assignment device data for standard/safety shared labels is processed in the same way as operation processing with standard
programs.
*2 Values for safety devices when the Safety CPU operating status changes are cleared or turn off, regardless of the safety operation
mode.
*3 If the safety operation mode is TEST MODE, output is based on the output hold and clear settings when the status of network modules
(RJ71GF11-T2) for which safety communication settings are specified is CPU STOP. (
Manual for network module used)
Operation processing with standard programs is the same as the following.
Page 88 Operation Processing When Operating Status Is Changed
Safety CPU operating status
Safety communications processing
RUN state
Executes the set safety communications.
STOP state
Executes the set safety communications, however, send data is turned off (0).
PAUSE state
Executes the set safety communications, however, send data is turned off (0).
Safety CPU
Operating
Status
Safety CPU processing
Safety program
External output
Safety device data
Other than SA\Y
SA\Y
STOP
RUN
Executes safety programs.
Outputs the value after safety
program execution.
Retains the safety device data
status immediately before the
RUN status. Clears safety local
devices.
Retains the SA\Y value
immediately before the RUN
status.
RUN
STOP
Executes up to the END
instruction and then stops.
Turns off all safety
communication outputs.
Retains the device data status
immediately before the STOP
status.
Turns off all SA\Y values.
RUN
PAUSE
Stops operation after the
execution of one scan.
Turns off all safety
communication outputs.
Retains the device memory
status immediately before the
PAUSE state.
Turns off all SA\Y values.
PAUSE
RUN
Executes the program from the
start.
Outputs the value after safety
program execution.
Retains the device data status
immediately before the RUN
status. Clears safety local
devices.
Retains the device data status
immediately before the RUN
status.
PAUSE
STOP
Operation remains stopped.
All safety communication
outputs remain off.
Retains the device data status
immediately before the STOP
status.
Retains the SA\Y value
immediately before the STOP
state.
STOP
PAUSE
Operation remains stopped.
All safety communication
outputs remain off.
Retains the device data status
immediately before the PAUSE
state.
Retains the SA\Y value
immediately before the PAUSE
state.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......