28 FUNCTIONS
28.3 Tracking Transfer
To transfer the annunciator (F), link special relay (SB), link special register (SW), file register (ZR), or refresh
data register (RD), specify the corresponding data in "Device/Label Detailed Setting" of "Tracking Device/
Label Setting". (
After setting "Transfer collectively", perform a test operation in the system design phase and check if the size
of tracking data is 1M words or smaller. If the size of the tracking data is larger than 1M words, a stop error
occurs when the CPU module is powered off and on or reset.
■
Detailed setting
Set devices and labels to be transferred for each tracking block (No.1 to 64) to be used.
[CPU Parameter]
[Redundant System Settings]
[Tracking Setting]
[Device/Label Detailed Setting]
Window
Displayed items
*1 Global labels with devices assigned are not transferred as global labels. They are transferred according to the tracking settings of the
assigned devices.
When setting devices and labels for tracking transfer, click the [Size Calculation] button to check if the tracking
data capacity in one scan is equal to or less than 1M words.
Item
Item
Description
Setting
range
Default
Device Detailed
Setting
Global Device Setting
Set global devices to be transferred. (
0.0K Word
Local Device Setting
Set whether to transfer local devices or not.
When "Transfer" is set, all the local devices are transferred.
For the devices that can be set as local devices, refer to the following.
Page 456 Devices that can be specified
• Do Not
Transfer
• Transfer
Do Not
Transfer
Label Detailed
Setting
Global Label Setting
Set whether to transfer global labels or not.
When "Transfer" is set, all the global labels assigned to the device/label
memory are transferred.
• Do Not
Transfer
• Transfer
Do Not
Transfer
Local Label Setting
Set whether to transfer local labels or not.
When "Transfer" is set, all the local labels are transferred.
• Do Not
Transfer
• Transfer
Do Not
Transfer
Block Size Setting
Calculates "Block Size Setting" of each tracking block and "Total" of the
setting capacity.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......